Analog Output Terminals
184
4. For user scaling, set the 0% value in the Scaling point 1 field, and set the
100% value in the Scaling point 2 field.
5. For offset compensation, set the offset value in the Scaling Offset field.
Also select either Default Scaling or User Scaling in the Scaling Type
field.
6. Return to the General Tab, click the Download Button, and then click the
Reset Button to reset the Unit.
7. Click the OK Button and exit the window.
Section 7-4