Analog Output Terminals
Internal Circuits
Wiring
Output Range and
Conversion Data
Output Range: 0 to 5 V
174
5. Click the OK Button and exit the window.
Analog GND
The negative terminals for output 0
and output 1 are connected internally.
The terminal wiring varies according to whether voltage or current output is
used.
V0
I0
NC
+
+
0
NC
NC
For voltage
For current
output on
output on
output 0
output 1
+
External
External
device
device
Note: The voltage or current output signal ranges
are set on the DIP switch or from the Configurator.
The digital values that are output are converted to analog data according to
the output range used, as shown below. When the value exceeds the output
range, the DA conversion data is fixed at the High Limit or Low Limit set value.
The values 0000 to 1770 hex (0 to 6,000) correspond to the voltage range 0 to
5 V. The output range is
5.25 V
5 V
0 V
8000
FED4 (−300)
−0.25 V
0000 (0)
I+
V+
I1
V1
+
+
1
NC
+
0.25 to 5.25 V.
1770
189C
(6000)
(6300)
Section 7-4
7FFF