Analog Input Terminals
Setting Using the
DeviceNet Configurator
1,2,3...
program that considers the transmission delay when the Hold Flag is turned
ON, then enables the peak/bottom hold values after a fixed time interval.
1. Double-click the icon of the Analog Slave to be set in the Main Window and
open the Edit Device Parameters Window. (From the Maintenance Mode
Window, click the right mouse button over the Slave icon and select Pa-
rameters and Edit.)
2. Select the Tab Page for the input where peak/bottom hold is to be set, and
select Peak/Bottom Hold under the Function Choice heading.
3. Return to the General Tab, click the Download Button, and then click the
Reset Button to reset the Unit.
4. To allocate the Hold Flags (output) in the default connection path, click the
General Tab and select Holding Value from the pull-down menu in the De-
fault Connection Path (Out) field.