Remote I/O Communications Characteristics
CVM1- and CV-series PLCs (Synchronous Mode)
Minimum I/O Response
Time
194
The minimum I/O response time occurs with the I/O timing shown in the fol-
lowing diagram.
PLC
Master Unit
Input
Output
T
T
:
The Input Slave's ON (OFF) delay (Minimum value: 0)
IN
T
:
The Output Slave's ON (OFF) delay (Minimum value: 0)
OUT
T
:
The Input Slave's communications time/Slave (Refer to page 198.)
RT-IN
T
: The Output Slave's communications time/Slave (Refer to
RT-OUT
page 198.)
T
:
The PLC's cycle time (instruction execution + peripheral servicing)
PLC0
Note Refer to SECTION 5 General-purpose Slaves and SECTION 6 Environment-
resistive Slaves for details on Input and Output Slaves' ON and OFF delay
times. Refer to Refresh Time on page 199 and the Operation Manual for the
PLC being used for details on the PLC's cycle time.
The minimum I/O response time (T
T
= T
+ T
MIN
IN
RT-IN
Cycle time
Instruction
Periph-
Periph-
eral ser-
eral ser-
execution
vicing
vicing
T
T
IN
RT-IN+
PLC0
) is the total of the following terms:
MIN
+ 2 × T
+ T
PLC0
RT-OUT
Section 8-1
Instruction
Periph-
Instruction
eral ser-
execution
execution
vicing
T
T
T
PLC0
RT-OUT
OUT
+ T
OUT