Omron DRT2 Series Operation Manual page 44

Devicenet slaves
Hide thumbs Also See for DRT2 Series:
Table of Contents

Advertisement

DeviceNet Remote I/O Communications
Method 3 can be performed by allocating real I/O data and Generic Status
Flags independently in the Master's connection path using the Configura-
tor. (This method can be used only with CS/CJ-series Master Units.)
Example of Allocation Using Method 2
The Generic Status Flags are as follows:
Bit
0
Basic Unit's I/O Power Status Bit
0: I/O power supply ON
1: I/O power supply OFF
1
Expansion Unit's I/O Power Status Bit
0: I/O power supply ON
1: I/O power supply OFF
2
Network Power Voltage Drops Bit
0: Normal (Higher than set monitor value)
1: Error (Same as or lower than set monitor value)
3
Unit Maintenance Bit
0: Within range (Lower than set monitor value)
1: Out of range (Same as or higher than set monitor value)
4
Sensor Disconnected Bit (Environment-resistive Input Terminals only)
0: Connected (all inputs connected)
1: Disconnected (one or more input is not connected)
5
Short-circuited Bit (Environment-resistive Terminals only)
0: Normal I/O (all I/O points normal)
1: Short-circuited I/O (one or more I/O point is short-circuited)
6
Operation Time Over Bit
0: Within range (all output-to-input sets are
lower than set monitor value)
1: Out of range (one or more output-to-
input set is same as or higher than set
monitor value)
7
Connected Component Maintenance Bit
0: Within range (all I/O points are lower than set monitor value)
1: Out of range (one or more I/O point is same as or higher than set monitor
value)
Master CPU Unit
IN Area
15
8
7
DRT2-series Slave
Status
15
14
13
1
0
Real inputs (e.g., 16 points)
Contents
Section 3-2
Real inputs: 16 points
0
Status: 8 points
Node address 1
See note 1.
See note 2.
27