Analog Input Terminals
Setting Using the
DeviceNet Configurator
1,2,3...
The following table shows the input ranges that support user adjustment.
Input range
0 to 5 V
–0.25 to 0.25 V
1 to 5 V
–0.8 to 1.2 V
0 to 10 V
–0.5 to 0.5 V
–10 to 10 V
–11 to –9.0 V
4 to 20 mA
3.2 to 4.8 mA
0 to 20 mA
–1.0 to 1.0 mA
1. Double-click the icon of the Analog Slave to be set in the Main Window and
open the Edit Device Parameters Window. (From the Maintenance Mode
Window, click the right mouse button over the Slave icon and select Pa-
rameters and Edit.)
2. Select the Tab Page for the input to be adjusted, and click the Adjustment
Button. (At the same time set the input range again.)
3. Input the voltage (or current) transmitted from the connected device to the
Unit's input terminal that is equivalent to the 100% value.
4. Click the Fix upper adjusting value Button, and input the adjusted value.
5. Input the voltage (or current) transmitted from the connected device to the
Unit's input terminal that is equivalent to the 0% value.
Low Limit
4.75 to 5.25 V
4.8 to 5.2 V
9.5 to 10.5 V
9.0 to 11 V
19.2 to 20.8 mA
19 to 21 mA
Section 7-3
High Limit
165