Omron DRT2 Series Operation Manual page 74

Devicenet slaves
Hide thumbs Also See for DRT2 Series:
Table of Contents

Advertisement

Remote I/O Terminal and Environment-resistive Terminal Functions
Setting Using the
DeviceNet
Configurator
1,2,3...
changes to ON until the input changes to ON.
ON
Output
OFF
ON
Input
OFF
Operation Time
Monitor
(Previous
value)
ON
Output
OFF
ON
Input
OFF
Output; Input; Measures
this time period.
4. The precision of the measured time is ±6 ms when the ON delay is 0, and
the ON delay time is then added.The display resolution for the measured
time (ON delay 10 ms: ±16 ms), is displayed in 2-ms units when the ON
delay is 2 ms or less, and in the measuring unit of the set ON delay time
when 3 ms or more. (If the ON delay is 5 ms, the display will be for 5 ms,
10 ms, 15 ms, and 20 ms.)
The method used to set values from the DeviceNet Configurator (Ver. 2.20 or
later) is described here.
1. Turn ON the power to the DRT2-series Smart Slave.
2. From the Main Window, open the Network Configuration Window and dou-
ble-click or click the right mouse button over the icon of the DRT2-series
Smart Slave to be set. Select Parameter and Edit to display the Edit De-
vice Parameters Window.
From the Maintenance Mode Window, click the right mouse button over the
icon of the DRT2-series Smart Slave to be set. Select Parameter and Edit
to display the Edit Device Parameters Window.
3. Select the Operation Time Tab.
t1
t3
t2
t1
t2
Section 4-3
t3
57