Omron DRT2 Series Operation Manual page 235

Devicenet slaves
Hide thumbs Also See for DRT2 Series:
Table of Contents

Advertisement

DeviceNet Explicit Messages
Note 1. The Attribute (7E Hex) is bit 7 of the Generic Status and so the size is fixed at 4 bytes and has the
following format.
+00
Size, 0002
+01
+02
IN+OUT combined, terminals 0 to 7
+03
IN+OUT combined, terminals 8 to 15
Note • Depending on the Unit size, not all bits are used.
• 14FF is returned for all Units except mixed I/O Units.
2. The Attribute (7E Hex) is bit 7 of the Generic Status and so the size is fixed at 10 bytes and has the
following format.
+00
Size, 0008
+01
+02
IN Area, terminals 0 to 7
+03
IN Area, terminals 8 to 15
+04
IN Area, terminals 16 to 24
+05
IN Area, terminals 25 to 31
+06
OUT Area, terminals 0 to 7
+07
OUT Area, terminals 8 to 15
+08
OUT Area, terminals 16 to 24
+09
OUT Area, terminals 25 to 31
Note Depending on the Unit size, not all bits are used.
218
Fixed
The bit turns ON when the set value is
exceeded.
Fixed
The bit turns ON when the set value is
exceeded.