Analog Input Terminals
Setting Using the
DeviceNet Configurator
1,2,3...
Scaling
Default Scaling
150
When the input value fluctuates frequently, averaging can be used to produce
a stable input value, as shown in the following diagram.
Input analog value
1. Double-click the icon of the Analog Slave to be set in the Main Window and
open the Edit Device Parameters Window. (From the Maintenance Mode
Window, click the right mouse button over the Slave icon and select Pa-
rameters and Edit.)
2. Select the Tab Page for the input where moving average processing is to
be performed, and select Moving Average under the Function Choice
heading.
3. Return to the General Tab, click the Download Button, and then click the
Reset Button to reset the Unit.
4. Click the OK Button and exit the window.
The default setting is used to perform AD conversion of analog input values,
scaling them to a count between 0 and 6,000. Scaling can be used to change
scaled values that correspond to the input signal range into other values
required by the user (industry unit values). Scaling also eliminates the need
for ladder programming in the Master to perform math operations. The follow-
ing two methods of input scaling can be used.
Analog input values (count values) are converted to the original voltage and
current values. The units used are mV or
Section 7-3
Actual input
Averaged input
µ
A. When default scaling is