Remote I/O Terminal and Environment-resistive Terminal Functions
OFF Response Time
Setting Using the
DeviceNet
Configurator
1,2,3...
50
When input data changes to OFF, the input data is read five times for the
period of the set interval (1/5 of the OFF response time). If all values are OFF,
the input is turned OFF. The OFF timing is delayed according to the length of
the OFF response time.
The input filter can also be used for ON/OFF delay operations.
To use a pulse shorter than the communications cycle time, set the OFF
response time to a value longer than the communications cycle time. (If the
input pulse is short, the input may remain ON.)
1
2
3
4
5
ON
OFF
Not all values are OFF
OFF
ON
OFF
OFF
ON
during the five samples,
so the input is regarded
Input data
as being ON.
ON
OFF
The method used to set values from the DeviceNet Configurator (Ver. 2.20 or
later) is described here.
1. Turn ON the power to the DRT2-series Smart Slave.
2. From the Main Window, open the Network Configuration Window and dou-
ble-click or click the right mouse button over the icon of the DRT2-series
Smart Slave to be set. Select Parameter and Edit to display the Edit De-
vice Parameters Window.
From the Maintenance Mode Window, click the right mouse button over the
icon of the DRT2-series Smart Slave to be set. Select Parameter and Edit
to display the Edit Device Parameters Window.
3. Select the IN Tab.
Enter a value for the ON response time and OFF response time, and then
click the OK Button.
4. Select the General Tab, click the Download Button, and then click the Re-
set Button to reset the Unit.
5. Click the OK Button.
Section 4-3
1
2
3
4
5
ON
OFF
OFF
OFF
OFF
OFF
OFF
All values are OFF for
all five samples, so the
Input data
input is regarded as
being OFF.
ON
OFF
ON delay time
(= input filter time)