Omron DRT2 Series Operation Manual page 197

Devicenet slaves
Hide thumbs Also See for DRT2 Series:
Table of Contents

Advertisement

Analog Output Terminals
I/O Data (Patterns)
Analog Output Data
(Instance 192)
Generic Status Flags
(Instance 121)
180
6. Click the OK Button and use the following window to confirm that I/O has
been allocated correctly.
7. Return to the General Tab, and click the Download Button.
8. Click the OK Button and exit the window.
Analog Output Data is used to allocate two words (four bytes) of output data in
the Master. The data format used when data in the Master is allocated is
shown below. Data is allocated as two's complements.
15
Analog output data for Output 0
Analog output data for Output 1
The Generic Status Flag bits are allocated for monitoring flags with mainte-
nance information (Network Power Voltage Monitor Flag, Unit Conduction
Time Monitor Flag, and Analog Cumulative Counter Flag). The following data
format is used when these flags are allocated in the Master (1 byte).
Bit 7
Bit 6
Bit 5
0
0
MRF
The details of each bit are shown in the following table.
Bit
Abbrevia-
Name
tion
0
---
---
1
---
---
2
NPW
Network Power Voltage Mon-
itor Flag
3
RHW
Unit Conduction Time Moni-
tor Flag
4
CCW
Analog Cumulative Counter
Flag
Bit 4
Bit 3
Bit 2
CCW
RHW
NPW
Details
Reserved. (Always 0.)
Reserved. (Always 0.)
Turns ON when the Network
power level drops below the
set monitor value.
Turns ON when the Unit ON
time exceeds the set monitor
value.
Turns ON when any of the
cumulated analog values
exceeds the set monitor
value.
Section 7-4
0
Bit 1
Bit 0
0
0