Omron DRT2 Series Operation Manual page 152

Devicenet slaves
Hide thumbs Also See for DRT2 Series:
Table of Contents

Advertisement

Analog Input Terminals
Setting Using the
DeviceNet Configurator
1,2,3...
Internal Circuits
the Configurator to set separate input signal ranges for each of the Inputs
0 to 3 if required.
2. When all the four inputs from 0 to 3 are not used, the number of AD con-
version points can be set using the Configurator to speed up the conver-
sion cycle for each input. Refer to 7-3-3 Functions and Settings and 7-3-4
Calculating the Conversion Cycle.
Use the following procedure to set the input range for each input using the
Configurator.
1. Double-click the icon of the Slave to be set in the Main Window and open
the Edit Device Parameters Window. (From the Maintenance Mode Win-
dow, click the right mouse button over the Slave icon and select Parame-
ters and Edit.)
2. Select the Tab Page for the input where the range is to be changed.
3. Select the desired range from the pull-down menu in the Input Range field.
4. Return to the General Tab, click the Download Button, and then click the
Reset Button to reset the Unit.
5. Click the OK Button and exit the window.
510 kΩ
250 Ω
510 kΩ
Analog GND
V+
I+
V−
AG
Section 7-3
135