Daikin VAM-FA8VE Technical Data Manual page 268

Heat reclaim ventilation
Table of Contents

Advertisement

2
11
266
• HRV • VKM-GA(M)V1
The right column of Table A shows
the duct diameter equivalent to this
pressure loss of the local feature.
Note that the values shown in the
table are for λ = 0.018. For other
values of the friction resistance coefficient (λ) to be used, use the following equation to find appropriate
conversion.
Table A
No.
Name
1
R bend, round duct
2
Straight bend, round duct
3
R bend, rectangular duct
4
Straight bend, rectangular duct
5
Pipe inlet (with round hood)
Pipe inlet
6
(with rectangular hood)
(Example)
IV
III
Ventilating fan intended for
0.5m
use with a ducted system
I
(For galvanized steel pipe with λ = 0.02, approximate value)
• HRV • Heat Reclaim Ventilation
le : equivalent straight pipe length of partial resistance...[m]
ζ
d : straight pipe diameter................................................ [m]
le =
d
λ
ζ : Local loss coefficient
Sketch
H/W
d
R
d
0.25
0.5
W
R
H
1.0
4.0
0.25
0.5
W
1.0
H
4.0
θ
θ
V
θ
θ
V
V
VI
5m
External hood
0.5m
(equivalent straight pipe length 9m)
Duct diameter φ100
Material: galvanized
steel pipe
II
Status
Loss
coefficient ζ
R/dR/W
0.5
0.90
0.75
0.45
1.0
0.33
1.5
0.24
2.0
0.19
1.30
0.5
1.25
0.75
0.60
1.0
0.37
1.5
0.19
0.5
1.10
0.75
0.50
1.0
0.28
1.5
0.13
0.5
1.00
0.75
0.41
1.0
0.22
1.5
0.09
0.5
0.96
0.75
0.37
1.0
0.19
1.5
0.07
1.25
1.47
1.50
1.38
20°
0.02
40°
0.03
60°
0.05
90°
0.11
120°
0.20
20°
0.13
40°
0.08
60°
0.12
90°
0.19
120°
0.27