Daikin VAM-FA8VE Technical Data Manual page 163

Heat reclaim ventilation
Table of Contents

Advertisement

• HRV • VKM-GA(M)V1
5.7.3
Fresh-up Operation
Both the excessive supply mode and the excessive exhaust mode are selectable.
This function creates a more comfortable air environment.
Detail
Major
effects
Application
Example
5.7.4
Proprietary Developed HEP Element
The heat exchanger element uses a High Efficiency Paper (HEP) that has superior moisture-absorption
and humidifying properties and doubles the current efficiency of moisture absorption. The heat exchanger
unit speedily recovers heat contained as latent heat (vapor). The element is made of a material with
superior flame-resistant properties and is treated with an anti-molding agent.
Operation of the heat exchanger element
30.6˚C
62% RH
32˚C
70% RH
Features
High air shielding
Even in the conventional less humidity conditions, maintaining the features of the material that can get
excellent moisture permeability, we have achieved high air shielding, by special processing in the step of
milling paper.
• HRV • Heat Reclaim Ventilation
Supply Fresh-up
(Excessive outdoor air supply)
Supply air volume can be set at a higher level
than the exhaust air by the remote controller.
Prevents inflow of toilet odor
Prevents inflow of outdoor air in winter
Offices, etc.
Portion of fresh-up
HRV
(VKM)
operation
Air exhaust
Air supply
Outdoor
Indoor
SA
27.4˚C
63% RH
RA
26˚C
50% RH
Integrally-formed liner
Polymer material
that inhibits air
permeability
Highly humid air
Less humid air
Moisture absorbing liquid
Polymer material that inhibits air permeability that treated on the surface of the heat exchanger
element restrains air permeability.
(Excessive exhaust air supply)
Exhaust air volume can be set at a higher level
than the supply air by the remote controller.
Prevents outflow of airborne bacteria from
rooms in a hospital
Prevents outflow of odors from rooms in a
nursing home
Hospitals, Nursing homes, etc.
Air exhaust
Normal
ventilation fan
Air supply
Portion of
exhaust
operation
SA
Integrally-
Temperature
formed liner
and humidity
RA
Air component
Moisture permeability mechanism
Moisture absorption
Move through capillary
Moisture release
Exhaust Fresh-up
HRV
(VKM)
Sick room
Floor area
(HC0013)
HEP anti-molding
2
5
161

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vkm-gamv1Vkm-gav1

Table of Contents