Daikin VAM-FA8VE Technical Data Manual page 121

Heat reclaim ventilation
Table of Contents

Advertisement

9
Control System
9-2
Basic patterns
9-2-2
Independent system
Control with two remote controls
Purpose and functions
• For control of one HRV unit (Also one group control is
possible)
Sophisticated operation and indication output are
possible from either local place or remote place by two
liquid crystal remote controls.
• Either one of two liquid crystal remote controls can be
used for all operations and indications.
(However, initial setting can only be carried out by the
master remote control)
Point
• The wiring to the remote controls must be branched from
the unit as shown in the diagram.
(Though the crossover between the master and slave
remote controls is acceptable, the work to put two wires
into the remote control takes time.)
Group control
Purpose and functions
• Simultaneous control of multiple HRV units (max. 16 units)
is available. (for application to such as a spacious room)
• All operation and individual setting can be carried out
from one remote control.
• In case the liquid crystal indicates malfunction, the
indication of HRV unit No. shows in the display.
(If another remote control is additionally installed, control
with two remote controls is possible.)
Point
• No address setting is required because address is
automatically set.
(The address is optionally allocated. The address No. can
be confirmed by setting to service mode "Forced fan
operation" and be checked whether the unit is in
operation or not.)
• HRV • VAM-FA8VE
• HRV • Heat Reclaim Ventilation
Example of wiring for control
J1 J2
JC
SS1
X11A
X9A
X10A
HRV unit
Remote control
for HRV unit
Note
1. The maximum allowable total length of wires to the
remote control is 500 m.
2. Simple remote controls cannot be used for control with
two remote controls.
The following setting is required
• Either one of two remote controls must be set as a slave
remote control.
Required optional accessories
• Liquid crystal remote control × 2
BRC301B61
Example of wiring for control
J1 J2
JC
F1 F2
J1 J2
X11A
SS1
SS1
X9A
X9A
X10A
X10A
P1 P2
HRV unit
HRV unit
P1 P2
Remote control
for HRV unit
Note
1. The maximum allowable total length of wires to the
remote control is 500 m.
2. One liquid crystal remote control is always required.
3. Simple remote controls cannot be used for control with
two remote controls.
The following setting is required
• No setting is required. (product is to be just as it was when
shipped from the factory)
Required optional accessories
• One set of liquid crystal remote control
BRC301B61
F1 F2
P1 P2
P1 P2
P1 P2
Main
Sub
Remote control
for HRV unit
(HC0023)
JC
F1 F2
J1 J2
JC
F1 F2
X11A
X11A
SS1
X9A
X10A
P1 P2
P1 P2
HRV unit
(HC0024)