Daikin VAM-FA8VE Technical Data Manual page 147

Heat reclaim ventilation
Table of Contents

Advertisement

10
Installation
10-7
Electrical wiring procedure
View seen from VRV
Terminal board for transmission
Wiring
IN OUT
P1 P2 F1 F2 T1 T2
1 2 1 2
Unit wiring
Clamp material
Remote controller
wiring
Field supplied wire
Earth terminal (attached)
Ground the shield part
of shielded wire.
Shield part
Wiring Example
Outdoor unit / BS unit
Power supply
1 ~ 50Hz
Swich box
Out
220 - 240V
1
2
L N
Indoor unit
HRV
L N
1
2
1
2
P1 P2 F1 F1 T1 T1
Indoor unit
Outdoor unit / BS unit
• All transmission wiring except for the remote control wires is polarized and must match the terminal symbol.
• Use screened wire in transmission wiring. Ground the shield of the shield wire to " ", at the grounding screw, with the C-cup washer.
• Sheathed wire materials may be used for transmission wiring, but they are not suitable for EMC (Electromagnetic Compatibility) (European
Directive).
• When using sheathed wire, electromagnetic compatibility must conform to Japanese standards stipulated in the Electric Appliance
Regulatory Act.
Transmission wiring need not be grounded when using sheathed wire.
• HRV • VAM-FA8VE
Terminal board for
power supply
Grounding
L N
terminal
Power supply
(attached)
wiring
Earth screw
(attached)
C-cup washer
(attached)
(HC0084)
Power supply
1 ~ 50Hz
220 - 240V
L N
HRV
P2 P1
F1 F2
J1
J2 JC
L N
transmission
wiring
• HRV • Heat Reclaim Ventilation
PRECAUTIONS
!
1. Do not connect wires of different gauge to the same power
supply terminal. Looseness in the connection may cause
overheating. When connecting more than one wire to the
power supply wiring, use a 2 mm
Same gauge wires
2. Keep total current of crossover wiring between indoor units
less than 12 A. When using two power wiring of gauge greater
2
than 2 mm
(φ 1.6), branch the line outside the terminal board
of the unit in accordance with electrical equipment standards.
The branch must be sheathed so as to provide an equal or
greater degree of insulation as the power supply wiring itself.
3. Do not connect wires of different gauge to the same
grounding terminal. Looseness in the connection may
deteriorate protection.
4. Keep the power supply wiring distant from other wires to
prevent noise.
5. For remote control wiring, refer to the "INSTALLATION
MANUAL OF REMOTE CONTROL".
Following items are figured as shown below
transmission wiring
P1
P2
HRV
P1
P2
Remote controller (HRV)
2
(φ 1.6) gauge wire.
Different gauge wires
P1
P2
HRV
(HC0085)
1
10
145