Daikin VAM-FA8VE Technical Data Manual page 263

Heat reclaim ventilation
Table of Contents

Advertisement

• HRV • VKM-GA(M)V1
Calculate air flow based on the required air flow per floor area
3
Required air flow (m
/h)
= Required air flow per floor area (m
Required air flow per floor area (1m
Room
Office
Shop
Beauty salon
Amusement room
Smoking room
Small meeting room
Dining room (commercial)
Kinds of ventilation
Building, parking area in a building, boiler room,
electric room, machine room, galley, warehouse, etc.
Required air flow based on CO
CO
is produced by human being's breathing, which means that the required air flow depends on the
2
number of persons staying therein and/or labor loads. To calculate air flow based on CO
the following equation.
100M
Q =
K-Ko
3
Q : Required air flow [m
/h · person]
3
/h · person] → see Table A
M : CO
production [m
2
K : CO
concentration limit in normal status [%] see Table B
2
Ko : CO
concentration in the atmosphere [%] (normally 0.03%)
2
Table A CO
Production Depending on Labor Burdens
2
Energy metabolic rate :
Labor burden
RMR
0
Sitting quietly
0~1
Very light work
1~2
Light work
2~4
Medium work
4~7
Heavy work
Table B Required Air Flow Based on Labor Burdens
CO
production
Energy
2
for calculation
metabolic rate
3
(m
/h · person)
for calculation
0.013
0
0.022
0.8
0.030
1.5
0.046
3.0
0.076
0.8
<Example>
Assumptions : CO
production
2
CO
concentration limit
2
100 × 0.030
Q =
= 25m
3
/h · person
0.15 – 0.03
3
Therefore, air flow of 25 m
/h · person is required.
• HRV • Heat Reclaim Ventilation
3
/m
2
· h) × Floor area (m
2
)
3
10m
/h
3
15m
/h
3
12m
/h
3
15m
/h
3
20m
/h
3
25m
/h
3
25m
/h
Exhaust
Exhaust
Mechanical ventilation
Supply
Mechanical ventilation
Supply
Room
Ventilation fan
Ventilation fan
Ventilation fan
production
2
CO
production
2
3
(m
/h · person)
0.0132
0.0132~0.0242
0.0242~0.0352
0.0352~0.0572
0.0572~0.0902
Labor burden
CO
limit = 0.10% CO
2
Sitting quietly
18.6
Very light work
31.4
Light work
43.0
Medium work
65.7
Heavy work
106.0
0.03 m
3
/h · person (light work)
0.15 vol%
2
)
Air flow rate
10m
15m
12m
15m
20m
25m
25m
Exhaust
Natural ventilation
Supply
Natural ventilation
Mechanical ventilation
Positive
Negative
pressure
pressure
Exhaust opening
Room
Room
Intake
Clean room, machine
cooling, etc
Kitchen, toilet, pantry, etc. in residential
housing, and copy room, etc.
production, use
2
CO
production for calculation
2
3
(m
/h · person)
0.013
0.022
0.030
0.046
0.074
3
Required air flow (m
/h · person)
limit = 0.15% CO
2
10.8
18.3
25.0
38.3
61.7
2
3
/h
11
3
/h
3
/h
3
/h
3
/h
3
/h
3
/h
Mechanical ventilation
Ventilation fan
limit = 0.20%
2
7.6
12.9
17.6
27.1
43.7
261