Initial Setting - Daikin VAM-FA8VE Technical Data Manual

Heat reclaim ventilation
Table of Contents

Advertisement

10
Installation
10-8

Initial setting

10-8-1 Initial setting by the remote control for indoor unit
Purpose
• Interlocked operation
Remote controller
for indoor unit
• When only the centralized controller is used.
Central remote controller
Notes:
When you make several field settings to one (or one group of) indoor unit(s), the item
repeated and it should be terminated to the "normal display" by the procedure of item
• HRV • VAM-FA8VE
Controller
• Remote control for indoor unit
a
UNIT No.
b
GROUP
SETTING
c
4
3
1
7
6
5
• BRC301B61
HRV
UNIT No.
CODE
4
5
GROUP
3
6
1 7
4 5
• HRV • Heat Reclaim Ventilation
d
e
2
The following describes the operating procedure
and settings.
1
3
2
A
3
hr
A
SETTING
FRESH UP
hr
4
BRC301B61
5
6
2
7
to
2
as last.
7
Operating procedure for initial setting
The following describes the
operating procedure and settings.
When in the normal mode, press
the "
" button for a minimum
of four seconds, and the FIELD
SET MODE is entered.
Select the desired MODE NO.
with the "
" button.
During group control, when
setting by each indoor unit
(mode No. 20, 21, 22 and 23
have been selected), push the
"
" button and select the
INDOOR UNIT NO. to be set.
(This operation is unnecessary
when setting by group.)
Push the "
" upper button
and select FIRST CODE NO.
Push the "
" lower button
and select the SECOND CODE
NO.
Push the "
" button once and
the present settings are SET.
Push the "
" button to return
to the NORMAL MODE.
Press the INSPECTION button for more than
four seconds to enter the local setting mode
when the unit is in the normal mode.
Use the VENTILATION MODE, AIR FLOW RATE
button to select the desired "mode number".
(The code display will blink.)
To make setting for individual unit under
group control (when mode no. 27, 28 or 29 is
selected), press TIMER SETTING ON / OFF
button to select the "unit No." for which the
settings are to be made. (This process is not
necessary when settings are made collectively
for the group.)
Press the top section of the TIMER button to
select the "setting switch No.".
Press the lower section of the TIMER button
to select the "setting position No.".
Press the PROGRAM / CANCEL button once
to enter the settings. (The code display will
stop blinking and light up.)
Press the INSPECTION button to return to
normal mode.
of the above setting procedure should be
6
1
10
(HC0093)
147