• HRV • VKM-GA(M)V1
Nighttime Free Cooling Operation
<Flow Chart>
Nighttime Free Cooling
Operating Condition
Air-conditioner Operation
<STOP>
Nighttime free cooling Operation
<ON>
Yes
Lapsed time setup
<2hr, 4hr, 6hr, 8hr>
No
From air-conditioner stop time
>
<Lapsed time>
<Setup time>
Yes
Fan operation & Temperature monitor
<5Min>
Yes
>
<Indoor temp.>
<Preset temp.+2˚C>
Yes
>
<Indoor temp.>
<Outdoor temp.>
Yes
Fan operation
<ON (H)or(U-H)tap>
5.3.2
Automatic Changeover to Efficient Operation Patterns
Operation automatically changes to the optimum pattern to suit conditions.
EA
OA
• HRV • Heat Reclaim Ventilation
Nighttime Free Cooling
Air-conditioner Operation
No
Temp. monitor operation time
<Indoor temp.>
<Indoor temp.>
No
Fan operation Lapsed time
No
<Lapsed time>
Cooling
Heat exchanger element
Exhaust fan
Damper
(heat recovery)
RA
Automatic
changeover
SA
Air supply fan
DX-coil (cooling)
Precedent Condition
Yes
<RUN>
No
Yes
>
<Lapsed time>
60hr
No
Yes
<
<Preset temp.>
=
No
Yes
<
<Outdoor temp.>
=
No
Yes
>
60Min
No
In between (bypass ventilation)
EA
RA
Automatic
changeover
OA
SA
Standard mode
Standby mode
<60 Min>
( Fan ON time is included )
Fan operation
<STOP>
Heating
Heat exchanger element
(heat recovery)
EA
RA
OA
SA
DX-coil (heating)
Humidifying
2
5