Daikin VAM-FA8VE Technical Data Manual page 117

Heat reclaim ventilation
Table of Contents

Advertisement

• HRV • VAM-FA8VE
Function
BRC301B61
• ON / OFF
• Ventilation mode (Auto / Heat Exchange / Bypass)
• Ventilating rate (High / Low)
• Fresh up mode (On / Off)
BRC301B61
• ON / OFF
• Ventilation mode (Auto / Heat Exchange / Bypass)
• Ventilating rate (High / Low)
• Fresh up mode (On / Off)
• Timer setting (On / Off)
• Indication of filter cleaning signal
• Digital indication of malfunction
• The HRV unit operates whenever the indoor unit is in
operation.
• Precool / preheat operation is also possible.
• Various settings are available by adding the HRV
remote controllers.
• HRV • Heat Reclaim Ventilation
Nos. of the unit controlled and length of wiring
• One remote controller operates each HRV unit.
• Remote control wiring can be extended up to 500 m
maximum.
• Control of one HRV with two remote controllers
• The maximum allowable total length of remote
controller wiring is 500 m.
• Up to 16 HRV units can be controlled with one liquid
crystal remote controller.
• The maximum total length of remote controller wiring
is 500 m.
• Control with two remote controllers is available.
• A maiximum of 16 units of indoor unit and HRV unit
can be controlled by the remote controller for indoor
unit. (If they are in the same group)
• Remote control wiring can be extended up to 500 m
maximum.
• A maximum of 16 units of indoor unit and HRV unit can
be controlled the operation by the remote controller
for indoor unit.
• Remote control wiring can be extended up to 500 m
maximum.
Cautions
• The wire for remote controller is not included as
standard accessories and should be arranged locally.
• By connecting the adapter PCB, the operation signal
can be taken out remotely.
• "Fresh-up operation" is possible by external input.
• The group control is not possible by the remote
controller for HRV unit.
• Same as operation from local place.
• It is necessary to set the Master / Slave changeover
switch in the remote controller.
• Two remote controller operation is not available with
simple remote controllers.
• Same as operation from local place.
• Group control is not available with a simple remote
controller.
• All the settings of HRVs in the same group are the same
(However, it is possible to fix the individual setting by
each unit)
• Make sure to set "ON" for direct ducting setting.
• The HRV cannot be operated independently to
prevent the dust, when the indoor unit is not in
operation. However, if the fan of indoor unit is in
operation, the HRV unit can be operated
independently.