Daikin VAM-FA8VE Technical Data Manual page 35

Heat reclaim ventilation
Table of Contents

Advertisement

7
Product Specification
7-2
Optional accessories
7-2-3
KRP2A51, KRP2A61: Wiring adapter for electrical appendices
• For demand control from input B
Position
Function when input A is ON
C
Remote controller rejected
(Same as position "5")
D
E
Last command priority
(Same as position "6")
F
• Forced thermostat OFF command
Forces indoor unit to operate the fan only
• Forced temperature shift command
The indoor unit operates at 2 C higher (cooling) or 2 C lower (heating) than the set temperature.
Notes:
• In zone control, operation is displayed as long as one indoor unit is running.
When in the last command priority mode, some units are not operation while ON.
• In such case, even if input A is ON, the unit and all other units in the same zone will stop.
4. When operating with dual momentary inputs from A and B
(Use a momentary input of 200 mili-sec or longer.)
Position
Function
Remote
7
controller
rejection
Central
8
priority
Stop by
remote
9
controller
acceptable
Remote
controller
A
acceptance/
rejection
Last
B
command
priority
Note:
• Doing constant input A with position 7 to A, it will be forced OFF function
(input A is ignored.)
• Constant input cannot use for input B with position B.
• HRV • VAM-FA8VE
Function when input B is ON
Forced thermostat OFF command
Forced temperature shift command
Forced thermostat OFF command
Forced temperature shift command
Contents when input A
is ON
Operation (remote
controller is normally
rejected)
Operation + remote
controller accepted
Operation + stop by
remote controller
acceptable (No operation
by the remote controller)
Remote controller
acceptance only (No
operation by the remote
location)
Operation (remote
controller is normally
accepted)
• HRV • Heat Reclaim Ventilation
Contents when
input A is OFF
Stop + remote
controller rejection
Stop (remote
controller normally
accepted)
1
7
(HC0126)
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: