9.9.2
Connecting Power Supply Wiring and Ground Wiring
2
9
238
• HRV • VKM-GA(M)V1
Pass the power supply wiring and the ground wiring through the wiring through-hole into the electrical
parts box and secure with the included clamping material after connecting the wires to terminal blocks.
(Refer to Fig. 17-1, 17-2)
〈 VKM-GAMV1 series 〉
Terminal block (X1M) details
Short-circuit wire
Remove when installing
the humidistat
(locally procured).
〈 VKM-GAV1 series 〉
Terminal block (X1M) details
Precautions when laying power supply wiring
[PRECAUTIONS]
[1] A circuit breaker capable of shutting down power supply to the entire system must be installed.
[2] A single switch can be used to supply power to units on the same system.
However branch switches, branch overload circuit interrupter must be selected carefully.
[3] Fit the power supply wiring of each unit with a switch and fuse as shown in the drawing.
COMPLETE SYSTEM EXAMPLE
Power supply
[4] Use round crimp-style terminals for connecting wires to the power supply terminal block.
If unavailable, observe the following points when wiring.
Do not connect wires of different gauge to the same power supply terminal.
(Looseness in the connection may cause overheating.)
Use the specified electric wire. Connect the wire securely to the terminal. Lock the wire down without
applying excessive force to the terminal. (Tightening torque: 131N·cm ±10%)
Attach insulation sleeve
Round crimp-style terminal
• HRV • Heat Reclaim Ventilation
1 2 L N
Clamp
(accessory)
L N
Clamp
(accessory)
VRV Outdoor unit
VRV
Indoor unit
VRV
Indoor unit
Remote controller
Grounging terminal
(M4 screws, spring
washers, cup washers)
Resin Clamp parts
Power supply wiring
Ground wiring
Wiring for the humidistat
Grounging terminal
(M4 screws, spring
washers, cup washers)
Resin Clamp parts
Power supply wiring
Ground wiring
Power supply wiring
Sheathed cable
(H05VV-03G)
Switch
Transmission wiring
Sheathed cable
Fuse
HRV (VKM)
HRV (VKM)
Electric wire
Fig. 17-1
Fig. 17-2