Daikin VAM-FA8VE Technical Data Manual page 177

Heat reclaim ventilation
Table of Contents

Advertisement

7
Product Specification
7 - 1 VKM-GAMV1
7 - 1 - 5 Wiring diagram
VKM50,80,100GAMV1
Power supply
220-240V
~
50 Hz
Control box
Indoor unit
A1P
Printed circuit board
A2P
Printed circuit board
A3P
Printed circuit board (adapter for wiring)
C1, C2
Capacitor (M1F)
F1U
Fuse ( , 10A, 250V) (A1P)
F1U
Fuse ( , 5A, 250V) (A2P)
F1U, F2U
Fuse ( , 5A, 250V) (A3P)
F1UT-F2UT Thermo switch
(152°C) (M1F, M2F built-in)
HAP
Light emitting diode
(service monitor-green) (A1P)
HAP
Light emitting diode
(service monitor-green) (A2P)
K1R~K3R
Magnetic relay (M1F) (A1P)
K4R~K6R
Magnetic relay (M2F) (A1P)
K7R
Magnetic relay (M1D) (A1P)
K8R
Magnetic relay (S1L)
KCR, KFR
Magnetic relay (A3P)
: Terminal block
,
: Connector
: Short circuit connector
: Terminal
: Field wiring
NOTES
1
In case of using central remote control, connect it to the unit in accordance with the attached instruction manual.
2
In case using wiring adapter, connect it to the unit in accordance with the attached installation manual.
3
When connecting the input wires from outside, fresh up control operation can be selected by remot control, in details, refer to the installation manual
attached the unit.
4
When connecting the input wires from outside, forced off or on/off control operation can be selected by remot control, in details, refer to the In case
of installation manual attached the unit.
5
In case installing a humidistat S1H (locally procured), remove the short circuit wiring between (1) and (2) as shown in the figure right.
6
Do not remove the short circuit connectors of X8A and X9A. The unit will not run if they are removed.
7
SS1 (A3P) has already been set to off at factory set. Humidifying becomes impossible, if the setting are changed.
8
SS1 (A1P) has already been set to 'nor', at factory set. The unit will not run if the setting are changed.
9
Use copper conductors only.
• HRV • VKM-GAMV1
Adapter PC board for wiring
External output
(optional accessories)
terminals
Note 2
Contact
capacity
AC220-240V
0.01~1.6A
Note 8
KHR, KHuR Magnetic relay (A3P)
KSR
Magnetic relay (Y1S)
M1D
Motor (damper motor)
M1F
Motor (supply air fan)
R1T
Thermistor (indoor air)
R2T
Thermistor (outdoor air)
R3T
Thermistor (inlet air into coil)
R4T, R5Y
Thermistor (liquid/gas pipe of coil)
S1L
Float switch (humidifier)
S1Q
Limit switch (damper motor)
SS1
Selector switch (for especially use) (A1P)
SS1
Selector switch (humidistat input) (A3P)
T1R
Transformer (220-240V/22V)
T2R
Transformer (220-240V/22V)
X1M
Terminal block (power supply)
X1M, X2M
Terminal block (control) (A3P)
X2M
Terminal block (control) (A1P)
X3M
Terminal block (control)
X17A, X19A Connector (relaying wire)
Colors:
• HRV • Heat Reclaim Ventilation
Note 7
Note 5
Note 6
Note 3
Input from
outside
X20A
Y1E
Y2S
SS1
Ry1
Ry2
Tes10
X11A
X18A
S1H
BLK:
Black
PNK:
BLU:
Blue
RED:
GRN:
Green
WHT: White
ORG:
Orange
YLW:
Note 5
Note 4
Input from outside
Note 1
Transmission wiring,
central remote control unit
Wired remote control
(optional accessory)
Connector (relaying wire)
Electronic expansion valve
Feed water solenoid valve
Optional accessories
Wired remote control
Select switch (main/sub)
Adaptor PC board for wiring (KRP50-2)
Magnetic relay (operation/stop)
Magnetic relay (for humidifier operation)
Terminal block (for external output)
Connector for optional parts
Connector (adapter power supply) (A1P)
Connector (wiring adapter for electrical
appendices) (A2P)
Local supplied parts
Humidistat
Pink
Red
Yellow
3D051310
2
7
175