Daikin VAM-FA8VE Technical Data Manual page 241

Heat reclaim ventilation
Table of Contents

Advertisement

• HRV • VKM-GA(M)V1
[5] Tightening torque for the terminal screws.
Treminal block for remote controller/Transmission wiring (X3M)
Power supply terminal block (X1M)
Ground terminal (M4)
〈Precautions when connecting the ground〉
When pulling the ground wire out, wire it so that it comes through the cut out section of the cup washer.
(An improper ground connection may prevent a good ground from being achieved.)
9.9.3
Remote Power Supply Wiring, Transmission Wiring, Computerised Control Wire
Pass the remote control wiring, the transmission wiring, and the computerised control wire into the
electric parts box through the through-hole and connect to the terminals on the X3M terminal block. After
connection, secure with the included cramping material. (Refer to Fig. 18)
Detail of terminal block (X3M)
[PRECAUTIONS]
Refer to the "Remote Controller Installation Manual" on how to install and lay the wiring for the remote
controller.
Do not, under any circumstances, connect the power wiring to the remote controller or transmission
wiring terminal block.
Doing so can destroy the entire system.
Connect the remote controller and transmission wiring their respective terminal blocks.
9.9.4
Wiring for the Humidity Regulator (Locally Procured)
<VKM-GAMV1 series only>
Pass into the electric parts box together with the power wire through the power wiring through-hole.
Remove the short-circuit wires (1 and 2) on the X1M terminal block and connect the wiring for the
humidity regulator.
Secure with cramping material together with the power wire. (Refer to Fig. 17-1)
Size
Length
External contact specifications Normally closed contact (Current tolerance 10mA – 0.5A)
〈VKM-GAMV1 series only〉
If using humidistat, install one per HRV unit.
Controlling more than one HRV unit with a single humidity controller may prevent normal humidity
operation and cause water leakage, etc.
• HRV • Heat Reclaim Ventilation
Use the correct screwdriver for tightening the terminal screws. If the blade of screwdriver is too small,
the head of the screw might be damaged, and the screw will not be properly tightened.
If the terminal screws are tightened too hard, screws might be damaged.
Refer to the table below for the tightening torque of the terminal screws.
Round crimp-style terminal
Spring washer, flat washer
Ground screw
Wiring specifications
0.75 - 1.25mm
MAX. 100m
CAUTION
Tightening torque (N·m)
Cut out section
P1 P2 F1 F2 T1 T2
FORCED
REMOTE
TRANSMISSION
CONTRL
WIRING
OFF
Sheathed wire (2 wire)
2
0.79 – 0.97
1.18 – 1.44
1.44 – 1.94
Cup washer
Clamp
(accessory)
Remote controller wiring
Transmission wiring
Fig. 18
2
9
239