Daikin VAM-FA8VE Technical Data Manual page 20

Heat reclaim ventilation
Table of Contents

Advertisement

7
Product Specification
1
7-1
Specifications
7-1-2
Electrical specifications
7
Model name
VAM150FA
VAM250FA
VAM350FA
VAM500FA
VAM650FA
VAM800FA
VAM1000FA
VAM1500FA
VAM2000FA
SYMBOLS:
MCA: min. circuit amps. (A)
MFA: max. fuse amps. (A) (See note 5)
FM: fan motor
FLA: full load amps. (A)
kW: fan motor rated output (kW)
NOTES:
1. Voltage range units are suitable for use on the electrical systems where the voltage supplied to the unit terminals is not below or above
the listed range limits.
2. Maximum allowable voltage variation between phases is 2 %.
3. MCA/MFA
MCA = 1.25 × FLA
MFA ≤ 4 × FLA
(VAM2000FA5/8VE is regarded as 2 × VAM1000FA5/8VE)
4. Select wire size based on the value of MCA.
5. Instead of the fuse, use the circuit breaker.
Specifications for field supplied fuses and wire
Model
Type
VAM150FA
VAM250FA
VAM350FA
VAM500FA
VAM600FA
VAM800FA
VAM1000FA
VAM1500FA
VAM2000FA
18
• HRV • VAM-FA8VE
Units
50Hz
60Hz
Power supply
Power supply
max.264V
max. 242V
min.198V
min.138V
+ FLA
(fm1)
(fm2)
Power supply wiring
Field supplied fuses
VE
15A
• HRV • Heat Reclaim Ventilation
Power supply
MCA
MFA
0.9
0.9
1.35
1.35
2.3
3.4
3.4
6.75
6.75
Wire
Size
Wire size must comply
H05VV-U3G
with local codes.
FM
kW
0.03 × 2
15
0.03 × 2
15
0.03 × 2
15
0.03 × 2
15
0.14 × 2
15
0.23 × 2
15
0.23 × 2
15
0.23 × 4
15
0.23 × 4
15
Transmission wiring
Wire
Shield wire (2 wire)
FLA
0.4 × 2
0.4 × 2
0.6 × 2
0.6 × 2
1.0 × 2
1.5 × 2
1.5 × 2
1.5 × 4
1.5 × 4
4D036862
Size
2
0.75 – 1.25 mm