Daikin VAM-FA8VE Technical Data Manual page 132

Heat reclaim ventilation
Table of Contents

Advertisement

9
Control System
1
9-3
Applicable patterns
9-3-3
Central control system (DCS302B61)
9
Collective operation [Adapter PCB for remote control KRP2A Series]
Purposes and functions
A maximum of 64 groups can be controlled the operation
of "ON / OFF" collectively. (For the individual control, use the
central remote control or the unified On / Off control.)
Cautions
1. Adapter PCB can be installed in any unit connected to
the central transmission line.
2. It cannot be used with other central control.
3. The setting of group number is not required.
4. The HRV unit judges the ventilation mode, individually.
Example control wiring
Connecting line can be
extended up to 150 m
maximum.
B1 B2 BC
PCB board KRP2A series
(installed in the indoor
X18A
P1 P2
Indoor unit
P1 P2
P1 P2
Indoor unit
P1 P2
130
• HRV • VAM-FA8VE
Remote control board
(local supply)
ON / OFF
No-voltage normally
open contact for
W1 W2 W3 W4
micro-current
F1 F2
J1 J2
JC
F1 F2
X11A
SS1
X9A
X10A
P1 P2
HRV unit
P1 P2
Remote control
for HRV unit
F1 F2
J1 J2
JC
F1 F2
X11A
SS1
X9A
X10A
P1 P2
HRV unit
• HRV • Heat Reclaim Ventilation
Switch setting of the HRV unit
The initial setting is required by the remote control for the
indoor unit or HRV unit.
Collective zone interlock setting
................................................."OFF" (as per factory setting)
The setting of switch on the PCB
Voltage / no-voltage changeover switch(SS1)
................................................. "no-voltage"
* Remote control mode changeover switch (RS1) should be
selected.
Optional accessories required
Adapter PCB for remote control KRP2A61
(HC0038)