Product Specification
1
7-2
Optional accessories
7-2-10 K-DGL100A, K-DGL150A, K-DGL200A, K-DGL250A: Air suction / discharge grill
7
Installation procedure
Before starting installation, attach the supplied packing to the adapter provided in the same package.
(Attach the packing to the adapter flange so that it will be set within the
periphery of the flange.)
For installing on a wooden frame
(Using ceiling joist)
1. Fabricate the wooden frame and attach it to the ceiling joist.
* If the joist is not strong enough to support the unit, use hanging bolts
as well.
Inner dimension
Wooden frame
2. Put the unit inside the wooden frame and fix the unit using the provided
tapping screws (long ones).
3. Attach the adapter to the body using the provided tapping screws (short
ones).
For suspending on anchor bolts
1. Attach the adapter to the body using the provided tapping screws (short
ones).
2. Fix the provided hook metals (2 pcs.) to the body using the four tapping screws (short ones).
3. Fix the body to the anchor bolts so that it stays horizontally level. (M8 or M10)
Hook metal fixing position
L ± 25
• 12.5 (Adjustable range)
80
• HRV • VAM-FA8VE
K-DGL200A
K-DGL100A
K-DGL150A
K-DGL250A
270
320
Approx. 30 mm (square)
Dimension table Unit: mm
Part No.
K-DGL100A
K-DGL150A
K-DGL200A
K-DGL250A
(HC0197)
• HRV • Heat Reclaim Ventilation
Reinforcing
material
385
L
M
N
160
300
169
200
350
214
280
415
214
280
415
214
Inner dimension
Tapping screw
Screw
Hook
metal
(HC0198)
Wooden frame
Ceiling joist
(HC0199)
(HC0200)
(HC0201)
(HC0202)