Daikin VAM-FA8VE Technical Data Manual page 150

Heat reclaim ventilation
Table of Contents

Advertisement

10
Installation
1
10-8
Initial setting
10-8-2 Setting procedure of group no. for centralized control
10
The following shows the procedure how to set the group number for the centralized control by the remote control for indoor unit
Purpose
When you use the central remote controller and
the unified On / Off controller, you have to set the
each unit connected to the central transmission
line.
<Example>
Central remote controller
ON / OFF controller
[1-00]
[1-01]
[1-03]
Remote controller
for indoor unit
Notes:
Do not duplicate the group number.
Be sure to supply the power to the remote controller side.
(It cannot be set without the power supply.)
.
148
• HRV • VAM-FA8VE
• Remote control for indoor unit
a
or
b
c
4
3
[1-02]
1
7
No necessary
• BRC301B61
5
4
3
6
1 7
• HRV • Heat Reclaim Ventilation
Control
UNIT No.
GROUP
SETTING
6
5
2
3
HRV
A
UNIT No.
hr
CODE
SETTING
A
GROUP
FRESH UP
hr
BRC301B61
4 5
2
Operating procedure
The following describes the
operating procedure and settings.
When in the normal mode, press
the "
" button for a minimum
of four seconds, and the FIELD
SET MODE is entered.
Select the desired MODE NO.
d
with the "
" button.
During group control, when
setting by each indoor unit
e
(mode No. 20, 21, 22 and 23
have been selected), push the
"
" button and select the
INDOOR UNIT NO. to be set.
(This operation is unnecessary
when setting by group.)
Push the "
" upper button
and select FIRST CODE NO.
Push the "
" lower button
and select the SECOND CODE
NO.
Push the "
" button once and
the present settings are SET.
Push the "
" button to return
to the NORMAL MODE.
The units in [ ] do not require the group no.
setting for the centralized controller connected to
the central transmission line.
(Auto-address setting)
Press the INSPECTION button for more than
1
four seconds.
2
Use the VENTILATION MODE, AIR FLOW RATE
to select the mode no. "00".
3
Use the top or lower section of the TIMER
button to set the group no. for the
centralized controller.
(When you use the unified ON / OFF
controller, it displays only the group no.
selected by the setting switch for zone
control.)
4
Press the PROGRAM / CANCEL button to
enter the setting group no. shown on the
display.
Press INSPECTION button to return to normal
5
mode.
(HC0094)