Daikin VAM-FA8VE Technical Data Manual page 24

Heat reclaim ventilation
Table of Contents

Advertisement

7
Product Specification
1
7-2
Optional accessories
7-2-1
BRC301B61: Remote control
7
7-2-1-1 Remote control mounting instructions
3. Wire the HRV unit.
Connect the terminals on the upper part of the
remote
controller (P1, P2) and the terminals of the HRV unit
(P1, P2).
(P1 and P2 do not have polarity.)
HRV unit
P2 P1
Ground the shielded
part on the HRV unit
P C Board
(Wired from the rear)
4. Reattach the upper part of remote controller.
Be careful not to pinch the wiring when attaching.
NOTE
1. The switch box and wiring for connection are not
included.
2. Do not directly touch the PC board with your hand.
When controlling one HRV unit with two remote controllers
Change the MAIN/SUB changeover switch setting as described below.
P C Board
Main Remote
Controller
(Factory Set)
"
" is displayed for about one minute when the power supply is turned on, and the remote controller cannot be
88
operated in some cases.
22
• HRV • VAM-FA8VE
HRV unit
P2 P1
Lower part
of Remote
controller
P C Board
Upper Part
of Remote
controller
(Wired from the top)
S
S
S
S
M
M
Sub Remote
Controller
• HRV • Heat Reclaim Ventilation
NOTE
When wiring, run the wiring away the
power supply wiring in order to avoid
receiving electric noise (external
noise).
Notch the part for the
wiring to pass through
with nippers, etc.
Wiring Specifications
Shield Wire (2 wire) (See NOTE 3)
Wiring Type
Size
0.75 – 1.25 mm
NOTE:
1. Peel the shield and sheath for the part that is to pass
through the inside of the remote controller case, as
shown in the figure below.
Peel the shield
and sheath.
2. Treat the terminal for the wire to be connected to the
remote controller so the shielded part doesn't touch any
other part.
3. Sheathed wire may be used for transmission wirings, but
they do not comply with EMC (Electromagnetic
Compatibility) (European Directive). When using
sheathed wire. EMC must conform to Japanese
standards stipulated in the Electric Appliance Regulatory
Act. (If using a sheathed wire, the grounding shown in
the figure on the left is unnecessary.)
First, begin fitting
from the clips at the
bottom.
Set one remote controller to "main," and the other
to "sub."
NOTE
• If controlling with one remote controller, be sure to set
it to "main."
• Set the remote controller before turning power
supply on.
p
2
(HC0112)
2P034150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vkm-gamv1Vkm-gav1

Table of Contents