7
Product Specification
7 - 2 VKM-GAV1
7 - 2 - 9 Installation
2
7 - 2 - 9 - 1 Installation method
7
VKM50GAV1
Heat insulator
(Locally procured)
EA
(Exhaust air to outdoors)
Round shape hood
(Locally procured)
OA
(Fresh air from outdoors)
Maintenance space for the heat exchanger
elements the air filters, fans and humidifier
ø200
Nominal diameter
(Locally procured)
OA
(Fresh air from outdoors)
EA
(Exhaust air to outdoors)
Sloping downards at a
gradient of the 1/100
VKM80GAV1
Heat insulator
(Locally procured)
EA
(Exhaust air to outdoors)
Round shape hood
(Locally procured)
OA
(Fresh air from outdoors)
Maintenance space for the heat exchanger
elements the air filters, fans and humidifier
ø200
Nominal diameter
(Locally procured)
OA
(Fresh air from outdoors)
EA
(Exhaust air to outdoors)
Sloping downards at a
gradient of the 1/100
202
• HRV • VKM-GAV1
Air suction grille
(Locally procured)
1688
Branch duct
(Locally procured)
Control box
Flexible duct
(Locally procured)
Inspection
Inspection
hatch
hatch
360 (In case of 450 inspection hatch)
140 (In case of 600 inspection hatch)
Refrigerant piping (gas pipe)
(ø12.7 flare connection)
A gradient of
more than 1/30
Refrigerant piping (liquid pipe)
(ø6.4 flare connection)
Suspension bolt
450 • 600
(Locally procured)
inspection hatch
RA
(Locally procured)
(Return air from room)
Air suction grille
(Locally procured)
1688
Branch duct
(Locally procured)
Silencer
(Locally procured)
Flexible duct
Control box
(Locally procured)
Inspection
Inspection
hatch
hatch
360 (In case of
450 inspection hatch)
140 (In case of
600 inspection hatch)
Refrigerant piping (gas pipe)
(ø12.7 flare connection)
A gradient of
more than 1/30
Refrigerant piping (liquid pipe)
(ø6.4 flare connection)
Suspension bolt
450 • 600
(Locally procured)
RA
inspection hatch
(Return air from room)
(Locally procured)
• HRV • Heat Reclaim Ventilation
Air discharge grille
NOTES
(Locally procured)
1
Leave space for servicing the unit and include inspection hatch.
(Always open a hole on the side of the control box so that the air
filters, heat exchange elements, and fans can easily be inspected
Heat insulator
and serviced.)
(Locally procured)
2
Install the two outdoor ducts with down slope (slope of 1/30 or more)
to prevent entry of rain water, also, provide insulation for three ducts
(outdoor ducts and indoor supply air duct) to prevent dew
condensation) (material: glass wool of 25mm thick).
Air discharge grille
3
Do not turn the unit upside down.
(Locally procured)
4
Make sure install drain piping, and insulate drain piping to prevent
dew condensation.
5
Keep the drain pipe short and sloping downwards at a gradient of at
least 1/100 to prevent air from forming.
6
Do not use a bent cap or a round hood as the outdoor hood if they
might get rained on directly (we recommend using a deep hood)
(optional accessory).
7
In areas where freezing may occur, always take steps to prevent the
pipes from freezing.
8
Do not place something which shouldn't be get wet at the below of
this unit. The dew would fall at following case, where humidity is 80%
more, or the exit of drain socket is choked up, or the air filter is very
dirty.
SA
(Supply air to room)
Air discharge grille
NOTES
(Locally procured)
1
Leave space for servicing the unit and include inspection hatch.
(Always open a hole on the side of the control box so that the air
Heat insulator
filters, heat exchange elements, and fans can easily be inspected
(Locally procured)
and serviced.)
2
Install the two outdoor ducts with down slope (slope of 1/30 or more)
to prevent entry of rain water, also, provide insulation for three ducts
(outdoor ducts and indoor supply air duct) to prevent dew
condensation) (material: glass wool of 25mm thick).
Air discharge grille
(Locally procured)
3
Do not turn the unit upside down.
4
Make sure install drain piping, and insulate drain piping to prevent
dew condensation.
5
Keep the drain pipe short and sloping downwards at a gradient of at
least 1/100 to prevent air from forming.
6
Do not use a bent cap or a round hood as the outdoor hood if they
might get rained on directly (we recommend using a deep hood)
(optional accessory).
7
In areas where freezing may occur, always take steps to prevent the
pipes from freezing.
8
Do not place something which shouldn't be get wet at the below of
this unit. The dew would fall at following case, where humidity is 80%
more, or the exit of drain socket is choked up, or the air filter is very
dirty.
SA
(Supply air to room)
3D051322