Daikin VAM-FA8VE Technical Data Manual page 122

Heat reclaim ventilation
Table of Contents

Advertisement

9
Control System
1
9-2
Basic patterns
9-2-3
The interlocked operation system
9
Single-group interlocked operation (Basic pattern)
Purposes and functions
• The remote control for indoor unit can control the
interlocked operation with the HRV unit, and it can make
an initial setting of the ventilation flow rate, the
ventilation mode changeover and fresh-up operation. The
HRV unit can independently be operated, even if the
indoor unit is not in operation.
Note
1. The remote control should be connected to the terminal
no. P1 and P2, the same as the group control wiring of
indoor units.
2. Since this is two remote control system (for Indoor unit
and HRV unit), the Master / Slave setting is required.
Remote control for
Indoor unit
HRV unit
Single-group interlocked operation (Direct duct connection)
Purposes and functions
• The operation of HRV unit is interlocked to the indoor
unit connected by the duct, which has a fresh air intake.
• It can reduce the number of outlets for supply air.
• The HRV unit cannot be operated independently to
prevent a reverse stream of fresh air to the suction side of
the indoor unit, unless the fan of indoor is in operation.
Note
1. The amount of fresh air to the indoor unit should be less
than 20% of the total air volume of the indoor unit. (If
the amount of fresh air is too much, the capacity of the
indoor unit may reduce and the operating sound might
be higher.)
2. The HRV unit can be operated independently, if the fan
of indoor unit is in operation.
3. Since this is two remote control system (for Indoor unit
and HRV unit), the Master / Slave setting is required.
Remote control for
Indoor unit
HRV unit
120
• HRV • VAM-FA8VE
Setting
Slave
Master
Setting
Slave
Master
• HRV • Heat Reclaim Ventilation
Example of control wiring
F1 F2
P1 P2
Indoor unit
P1 P2
Up to 500 m maximum
Switch setting for HRV unit
• No change is required. (as per factory setting)
Optional accessories required
• None
Example of control wiring
F1 F2
P1 P2
Indoor unit
P1 P2
Up to 500 m
Remote control
for indoor unit
Switch setting for HRV unit
The initial setting by the remote control for indoor unit
Direct duct setting .................... "ON" [17(27)·5·02]
Optional accessories required
• None
J1 J2
JC
F1 F2
X11A
SS1
X9A
X10A
P1 P2
HRV unit
Remote control
P1 P2
for HRV unit
(HC0025)
J1 J2
JC
F1 F2
X11A
SS1
X9A
X10A
P1 P2
HRV unit
Remote control
P1 P2
for HRV unit
(HC0026)