Daikin VAM-FA8VE Technical Data Manual page 27

Heat reclaim ventilation
Table of Contents

Advertisement

7
Product Specification
7-2
Optional accessories
7-2-3
KRP2A51, KRP2A61: Wiring adapter for electrical appendices
To host computer
monitor panel etc.
Notes:
Individual indoor units connected to the centralized line cannot be displayed individually.
Names of parts and functions
Microcomputer normal monitor
(HAP: GREEN)
Flickers when the microcomputer
is operating normally.
Power supply connector (D1, D2)
To adapter power supply connector
(X18A)
Transmission wiring (F1, F2)
To F1 and F2 on indoor unit terminal
board
Input changeover switch (SS1)
(Factory set: VOLT)
Set according to the type of input (voltage/
non- voltage) sent to remote control input
terminal board (X1M).
• HRV • VAM-FA8VE
Max. 64 groups
To outdoor unit
Trouble monitor (H10P: RED)
Lights up when trouble occurs
in electrical wiring or parts.
Remote control is disabled.
(LED is out in normal
B1
Remote control input
terminal board (X1M)
Connects control input from
remote (host computer
monitor panel, timer, etc.).
• HRV • Heat Reclaim Ventilation
Remote controller
W1
W2
W3
W4
+
B2
BC
A
A
Temperature setting input terminals (A
Temperature setting is determined by a
resistance value between 0 and 135 Ω.
NEVER apply voltage to this terminal for
any reason whatsoever.
Indoor unit
Max. 16 unit
Max. 16 unit
Display output terminal board (X2M)
Connects operation and error output to a
remote
point (host computer monitor panel, etc.).
Control mode selector switch (RS1)
(Factory set: 0)
For selecting how to operate the
system via remote.
Temperature setting ON/OFF switch (SS2)
(Factory set: P)
To enable temperature setting with the
I
remote controller, set to "Inhibit".
P
To set temperature setting only by
remote control, set to "Permission".
SS3
Display output switch (SS3) (Factory set: Z)
To display all control units as unified
Z
zone, set to "Zone".
I
Note: Do not set to "Individual".
SS3
This will cause a system error (H10P
(Factory set)
flashes.)
For details,
+
,
see the wiring
diagram
1