Brazil - Emerson Rosemount 5408 Reference Manual

Level transmitters, non-contacting radar with hart protocol
Hide thumbs Also See for Rosemount 5408:
Table of Contents

Advertisement

Product certifications
February 2020
Temperature class /
Maximum surface
temperature
T2
T3
T4
B.13

Brazil

B.13.1
E2 INMETRO Flameproof
Certificate
Standards
Markings
Specific Conditions of Use (X):
1. See certificate.
B.13.2
I2 INMETRO Intrinsic Safety
Certificate
Standards
Markings
Safety parameter
Voltage U
Current I
Power P
Capacitance C
Inductance L
Specific Conditions of Use (X):
1. See certificate.
228
Ambient temperature range
-34 °C ≤ Ta ≤ 70 °C
-34 °C ≤ Ta ≤ 70 °C
-34 °C ≤ Ta ≤ 70 °C
UL-BR 17.0344X
ABNT NBR IEC 60079-0:2013, ABNT NBR IEC 60079-1:2016, ABNT NBR
IEC 60079-26:2016, ABNT NBR IEC 60079-31:2014
Ex db IIC T6...T2 Ga/Gb
Ex tb III C T85°C...T250°C Db
Tamb = -60 °C to +70 °C; IP6X
UL-BR 17.0344X
ABNT NBR IEC 60079-0:2013, ABNT NBR IEC 60079-11:2013, ABNT NBR
IEC 60079-26:2016, ABNT NBR IEC 60079-31:2014
Ex ia IIC T4...T2 Ga
Ex ib IIC T4...T2 Ga/Gb
Ex ia IIIC T85°C...T250°C Da
Tamb = -60 °C to +70 °C
i
i
i
i
i
Process temperature range
-34 °C to 250 °C
-34 °C to 195 °C
-34 °C to 130 °C
®
HART
30 V
133 mA
1.0 W
7.3 nF
0