Service and troubleshooting
February 2020
Procedure
1. In Rosemount Radar Master Plus, under Configure, select Level Setup → Advanced.
2. Under More Advanced Options, select Empty Tank Handling.
3. In the Empty Tank Handling list, select User Defined.
4. Select the Bottom echo visible when tank is empty check box.
5. Select Save.
7.5.3
Handling ghost echoes in still pipes
The Track First Echo function can eliminate ghost echo problems below the product
surface. When enabled, the first echo above threshold will always be considered as the
surface echo.
Ghost echoes may occur in still pipes because of multiple reflections between the pipe
wall, flange, and antenna. In the echo curve, these echoes appear as amplitude peaks at
various distances below the product surface, see
Figure 7-13: Ghost Echoes in Still Pipes
A. Signal amplitude
B. Actual level
C. Virtual level
D. Distance
136
Reference Manual
00809-0100-4408
Figure
7-13.
Reference Manual