Emerson Rosemount 5408 Reference Manual page 127

Level transmitters, non-contacting radar with hart protocol
Hide thumbs Also See for Rosemount 5408:
Table of Contents

Advertisement

Reference Manual
00809-0100-4408
7.4.5
Calibrate analog out
Calibrate analog out using Rosemount Radar Master Plus
Use this function to calibrate the analog output by comparing the actual output current
with the nominal 4 mA and 20 mA currents. Calibration is done at factory and the analog
output does not normally need to be recalibrated.
Procedure
1. Under Service Tools, select Maintenance → Routine Maintenance.
2. Select Calibrate Analog Out and follow the on-screen instructions.
Calibrate analog out using AMS Device Manager and
handheld communicator
Use this function to calibrate the analog output by comparing the actual output current
with the nominal 4 mA and 20 mA currents. Calibration is done at factory and the analog
output does not normally need to be recalibrated.
Procedure
1. Select Service Tools → Maintenance → Routine Maintenance.
2. Select D/A trim and follow the on-screen instructions.
Rosemount 5408 and 5408:SIS Level Transmitters
c) Turn the jam screw counterclockwise until it contacts the cover.
Required for explosion-proof/flameproof installations only.
d) Turn the jam screw an additional ½ turn counterclockwise to secure the
cover.
Service and troubleshooting
February 2020
127