C.3.3
Volume
Select if the volume measurement should be calculated from the configured tank
dimensions or a strapping table.
Strapping tables can be used for irregularly shaped tanks, to eliminate errors due to
bulging when product is added to a tank, or if a pre-defined tank type does not provide
sufficient accuracy.
Strapping table
Strapping table requires entering level-volume pairs in a table (maximum 50 points). Use
most of the strapping points in regions where the tank shape is non-linear. Starting at the
bottom of the tank, for each new point, enter the total volume up to the specified level
value.
Volume offset
Use this parameter to add a volume to each calculated volume value, for example a sump
volume below the Zero Level in the tank.
C.3.4
Scaled variable
The scaled variable can be used to convert a transmitter variable into an alternative
measurement, such as open channel flow, mass, or calibrated level (e.g. 5 point
verification). This variable is available only for transmitters ordered with Smart Diagnostics
Suite (option code DA1).
The scaled variable is defined by creating a table of transmitter variables and
corresponding output variables. A maximum of 50 points can be specified. Between the
points linearly interpolated values are calculated.
Figure C-15: Scaled Variable Examples
Input Variable:
Level
Volume
Level
As an example, consider a product with a density of 900 kg/m
mass conversion is given by the following table:
Table C-2: Example of Scaled Variable Table
Number
1
2
Rosemount 5408 and 5408:SIS Level Transmitters
Output Variable:
Flow
Mass
Calibrated Level
Input value (volume)
3
0 m
3
100 m
Configuration parameters
February 2020
3
. In this case, the volume to
Output value (mass)
0 ton
90 ton
263