Configuration parameters
February 2020
Table C-1: Percent of range auxiliary
Parameter
Percent of range auxiliary
100% auxiliary
0% auxiliary
C.2.2
Units
The units for length, volume, temperature, and level rates are selectable. All configuration
parameters and transmitter variables will be expressed in these units.
Related information
Output units
C.2.3
Analog output
The output source (primary variable), range values, and alarm mode are specified for the
analog output.
Primary variable
Select the desired transmitter variable to use for the analog output.
Upper/lower range value
Enter the range values that correspond to the analog output values 4 and 20 mA. The
transmitter will drive the output to saturation mode if a measured value goes outside the
4-20 mA range values.
Note
Measurements may not be possible in the blind zone, and measurements close to the
blind zone will have reduced accuracy. Therefore, the 20 mA point should be configured
outside these zones.
252
Description
The variable selected for percent of range
auxiliary.
Value corresponding to 100 percent range of
variable selected for percent of range auxiliary.
Value corresponding to 0 percent range of
variable selected for percent of range auxiliary.