Service and troubleshooting
February 2020
Table 7-2: Configuration Error Details
Host diagnostic message
Geometry Configuration
Error
Primary Variable
Configuration Error
Measurement Correction
Configuration Error
Threshold Configuration Error The surface threshold configuration is
Factory Approval Error
SIS Configuration Error
104
(continued)
Description
The configured tank geometry results in a
too large level measuring range for this
device.
The Primary Variable selection is not
supported.
Note
Rosemount 5408:SIS only supports level or
distance as Primary Variable.
The factory measurement correction data
is invalid.
incorrect.
The Sensor Module factory approval is
missing.
The Transmitter factory approval is
missing.
It is currently not possible to enable Safety
Mode due to other active alerts.
Note
Rosemount 5408:SIS only supports liquids
level measurement when operating in
Safety (SIS) mode.
Reference Manual
00809-0100-4408
Recommended actions
1. Check tank geometry configuration
and reduce Reference Height.
2. If condition persists, restore default
settings and reconfigure the device.
1. Change Primary Variable to variable
supported by device.
2. Consider purchasing an upgrade of
the device to access additional
variables.
1. Restore default settings and
reconfigure the device.
2. If the condition persists, replace the
device.
Rosemount Radar Master Plus:
1. Adjust the threshold as necessary.
2. If condition persists, restore default
settings and reconfigure device.
AMS Device Manager and handheld
communicator:
1. In the threshold table, check that
distance-threshold values are entered
in increasing order.
2. Check that the number of threshold
points to use is correct.
3. If condition persists, restore default
settings and reconfigure the device.
1. Restart the device.
2. Restore default settings and
reconfigure device.
3. If the condition persists, replace the
device.
1. Clear other active alerts by priority
order until this alert is cleared.
2. Change Operational Mode to Control/
Monitoring if device is not intended to
be used as safety device.
3. If the condition persists, restore
default settings and reconfigure
device.