The most effective grounding method is direct connection to earth ground with minimal
impedance. There are two grounding screw connections provided (see
Figure 4-1: Ground Screws
A. Internal ground screw
B. External ground screw
Cable shield grounding
Make sure the instrument cable shield is:
Trimmed close and insulated from touching the transmitter housing.
Continuously connected throughout the segment.
Connected to a good earth ground at the power supply end.
Figure 4-2: Cable Shield
A. Insulate shield and drain wire
B. Minimize distance
C. Trim shield and insulate exposed drain wire
D. Connect drain wire to the power supply ground
Note
Do not ground the shield and its drain wire at the transmitter. If the cable shield touches
the transmitter housing, it can create ground loops and interfere with communications.
Rosemount 5408 and 5408:SIS Level Transmitters
Electrical installation
February 2020
Figure
4-1).
75