Product Certifications
November 2016
Special Condition for Safe Use (X):
1. If the equipment is fitted with an optional 90 V
transient suppressor, it is incapable of withstanding
the 500 V isolation from earth test and this must be
taken into account during installation.
2. The enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however
care should be taken to protect it from impact and
abrasion when located in Zone 0.
IG
IECEx FISCO
Certificate: IECExBAS08.0045X
Standards: IEC60079-0:2011, IEC60079-11:2011
Markings: Ex ia IIC T4 Ga (–60 °C
Table B-6. Input Parameters
Parameter
Voltage U
i
Current l
i
Power P
i
Capacitance C
i
Inductance L
i
Special Condition for Safe Use (X):
1. If the equipment is fitted with an optional 90 V
transient suppressor, it is incapable of withstanding
the 500 V isolation from earth test and this must be
taken into account during installation.
2. The enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however
care should be taken to protect it from impact and
abrasion when located in Zone 0.
134
T
+60 °C)
a
FISCO
17.5 V
380 mA
5.32 W
0 μF
0 mH
N7
IECEx Type n
Certificate: IECExBAS08.0046X
Standards: IEC60079-0:2011, IEC60079-15:2010
Markings: Ex nA IIC T4 Gc (–40 °C
Special Condition for Safe Use (X):
1. If fitted with a 90 V transient suppressor, the
equipment is not capable of withstanding the 500 V
electrical strength test as defined in clause 6.5.1 of
IEC60079-15:2010. This must be taken into account
during installation.
B.6 Brazil
E2
INMETRO Flameproof
Certificate: UL-BR 14.0375X
Standards: ABNT NBR IEC60079-0:2008 + Errata
1:2011, ABNT NBR IEC 60079-1:2009 +
Errata 1:2011,ABNT NBR IEC
60079-26:2008 + Errata 1:2009
Markings: Ex d IIC T6/T5 Gb IP66,
T6(–50 °C
T5(–50 °C
Special Condition for Safe Use (X):
1. The device contains a thin wall diaphragm.
Installation, maintenance and use shall take into
account the environmental conditions to which the
diaphragm will be subjected. The manufacturer's
instructions for installation and maintenance shall be
followed in detail to assure safety during its expected
lifetime.
2. The Ex d blanking elements, cable glands, and wiring
shall be suitable for a temperature of 90 °C
3. In case of repair, contact the manufacturer for
information on the dimensions of the flameproof
joints.
I2
INMETRO Intrinsic Safety
Certificate: UL-BR 14.0759X
Standards: ABNT NBR IEC 60079-0:2008 + Errata
1:2011; ABNT NBR IEC 60079-11:2009
Markings: Ex ia IIC T4 Ga (–60 °C
Table B-7. Input Parameters
Parameter
HART
Voltage U
30 V
i
Current l
200 mA
i
Power P
i
0.012 μF
Capacitance C
i
Inductance L
0 mH
i
Reference Manual
00809-0300-4101, Rev BB
T
+70 °C)
a
T
+65 °C),
a
T
+80 °C)
a
T
+70 °C)
a
Fieldbus/PROFIBUS
30 V
300 mA
1 W
1.3 W
0 μF
0 mH
Product Certifications