Export echo curve movies
Procedure
1. Under Service Tools, select Echo Curve.
2. Select Export.
3. Type your desired file name.
4. Browse to the desired directory, and then select Save.
5. Under Time range, select Last 1 hour, Last 3 hours, Last 24 hours, or User defined
6. If User defined range is selected, specify the start and end times.
7. Select Export.
8. Select Back.
Set echo curve range
Procedure
1. Under Service Tools, select Echo Curve.
2. Select Options.
3. Under Echo Curve Range, select User Defined.
4. Enter the desired values.
5. Select Save.
6. Select Back.
Set timeline resolution
To set the resolution of the level trend timeline:
Procedure
1. Under Service Tools, select Echo Curve.
2. Select Options.
3. In the Timeline Resolution list, select the desired length (in hours) of the timeline.
4. Select Save.
5. Select Back.
Rosemount 5408 and 5408:SIS Level Transmitters
range.
Service and troubleshooting
February 2020