3.5.8
Align transmitter head
Procedure
1. Loosen the nut slightly and turn the transmitter.
2. Verify the transmitter head is properly aligned.
Rosemount 5408 and 5408:SIS Level Transmitters
60 mm
Option
Description
Open tank Align the marking on the sensor module toward the tank wall (see
Figure
3-13).
Still pipe
Align the external ground screw toward the holes of the still pipe (see
Figure
3-14).
Chamber
Align the external ground screw toward the process connections (see
Figure
3-15).
Mechanical installation