Usa - Emerson Rosemount 5408 Reference Manual

Level transmitters, non-contacting radar with hart protocol
Hide thumbs Also See for Rosemount 5408:
Table of Contents

Advertisement

Product certifications
February 2020
B.9

USA

B.9.1
E5 Explosionproof (XP), Dust-Ignitionproof (DIP)
Certificate
Standards
Markings
Specific Conditions of Use (X):
1. Flamepath joints are not for repair. Contact the manufacturer.
2. Plastic wire-on tag, Plastic part of Process Seal Antenna and Non-standard paint
3. Appropriate cable, glands, and plugs need to be suitable for a temperature of 5 °C
4. The Transmitter can be installed in the boundary wall between a Zone 0 and Zone 1
5. Cable entries must be used which maintain the ingress protection of the enclosure
6. Install per Control drawing D7000002-885.
7. Using the box provided on the nameplate, the User shall permanently mark the
8. Display glass shall be positioned in such a way as to minimize the risk of mechanical
9. The applicable temperature class, ambient temperature range and process
(20)
Other temperature ranges may apply, see Specific Conditions of Use (X).
214
FM-US FM16US0010X
FM Class 3600 – 2018; FM Class 3615 – 2018; FM Class 3810 – 2005;
ANSI/ISA 60079-0 – 2013; ANSI/UL 60079-1 – 2015; ANSI/UL 60079-26
– 2017; ANSI/ISA 60079-31 – 2015; ANSI/NEMA
60529 – 2014, ANSI/ISA 12.27.01:2011
XP CL I, DIV 1, GRPS A, B, C, D T6...T2
DIP CLII/III, DIV 1, GRPS E, F, G; T6...T3
CL I Zone 0/1 AEx db IIC T6...T2 Ga/Gb
Zone 21 AEx tb IIIC T85 °C...T250 °C Db
(-40 °C ≤ Ta ≤ +70 °C)
SINGLE SEAL
options (paint options other than Rosemount Blue) may cause risk from
Electrostatic discharge. Avoid installation that could cause electrostatic build-up,
and only clean with a damp cloth.
greater than the maximum specified ambient temperature for location where
installed.
area. In this configuration, the process connection is installed in Zone 0, while the
transmitter housing is installed in Zone 1. Refer to Control Drawing D7000002-885.
to at least IP6X and/or Type 4X rating. To maintain the ingress protection ratings,
Covers and Sensor Module to be fully tightened and PTFE tape or pipe dope is
required for cable entries and blanking plugs. See Instruction Manual on application
requirements.
type of protection chosen for the specific installation. Once the type of protection
has been marked it shall not be changed.
impact.
temperature range of the equipment is as follows:
(20)
; Type 4X/IP6X
Reference Manual
00809-0100-4408
®
250 – 1991; ANSI/IEC
Reference Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 5408:sis

Table of Contents