Emerson Rosemount 5408 Reference Manual page 222

Level transmitters, non-contacting radar with hart protocol
Hide thumbs Also See for Rosemount 5408:
Table of Contents

Advertisement

Product certifications
February 2020
Specific Conditions of Use (X):
1. Flamepath joints are not for repair. Contact the manufacturer.
2. Plastic wire-on tag, Plastic part of Process Seal Antenna and Non-standard paint
3. Appropriate cable, glands, and plugs need to be suitable for a temperature of 5 °C
4. The Transmitter can be installed in the boundary wall between EPL Ga and EPL Gb
5. Cable entries must be used which maintain the ingress protection of the enclosure
6. Install per Control Drawing D7000002-885.
7. Using the box provided on the nameplate, the User shall permanently mark the
8. Display glass shall be positioned in such a way as to minimize the risk of mechanical
9. The applicable temperature class, ambient temperature range and process
Temperature class /
Maximum surface
temperature
Gas & Dust groups:
T2 / T250°C
T3 / T200°C
T4 / T135°C
T5 / T100°C
T6 / T85°C
B.11.2
I1 ATEX Intrinsic Safety
Certificate
Standards
222
-60 °C ≤ Ta ≤ +70 °C
options (paint options other than Rosemount Blue) may cause risk from
Electrostatic discharge. Avoid installation that could cause electrostatic build-up,
and only clean with a damp cloth.
greater than the maximum specified ambient temperature for location where
installed.
location. In this configuration, the process connection is EPL Ga, while the
transmitter housing is EPL Gb. Refer to Control Drawing D7000002-885.
to at least IP6X. To maintain the ingress protection ratings, Covers and Sensor
Module to be fully tightened and PTFE tape or pipe dope is required for cable entries
and blanking plugs. See Instruction Manual on application requirements.
type of protection chosen for the specific installation. Once the type of protection
has been marked it shall not be changed.
impact.
temperature range of the equipment is as follows:
Ambient temperature range
-60 °C ≤ Ta ≤ 70 °C
-60 °C ≤ Ta ≤ 70 °C
-60 °C ≤ Ta ≤ 70 °C
-60 °C ≤ Ta ≤ 70 °C
-60 °C ≤ Ta ≤ 70 °C
FM15ATEX0055X
EN IEC 60079-0:2018, EN 60079-11:2012, EN 60079-26:2015, EN
60529:1991+A1:2000 +A2:2013
Reference Manual
00809-0100-4408
Process temperature range
-60 °C to 250 °C
-60 °C to 195 °C
-60 °C to 130 °C
-60 °C to 95 °C
-60 °C to 80 °C
Reference Manual