Service and troubleshooting
February 2020
7.4.10
View input registers
View input registers using Rosemount Radar Master Plus
Measured data is continuously stored in the input registers. By viewing the contents of the
input registers, expert users can check that the transmitter works properly.
Procedure
1. Under Configure, select Level Setup → Advanced.
2. Under More Advanced Options, select Expert Options.
3. Select the Input Registers tab.
4. Under Show registers by, do one of the following:
5. Select Refresh.
View input registers using AMS Device Manager and
handheld communicator
Measured data is continuously stored in the input registers. By viewing the contents of the
input registers, expert users can check that the transmitter works properly.
Procedure
1. Select Configure → Manual Setup → Level Setup → Advanced → Expert Options
2. Type the desired register number to start reading from.
3. Select Read Input Registers. 10 registers will be read, starting from the selected
4. (Handheld communicator) Select Input Registers.
7.4.11
View/edit holding registers
View/edit holding registers using Rosemount Radar Master
Plus
The holding registers store various transmitter parameters, such as configuration data,
used to control the measurement performance.
Prerequisites
Note
Do not use holding registers to configure the transmitter unless you are qualified. This
dialog is mainly used for service purposes and for advanced configuration.
130
Select Block, and then in the list, select the desired register group.
Select Number, and then type the desired register number and the number of
registers.
→ Input Registers.