Emerson Rosemount 5408 Reference Manual page 103

Level transmitters, non-contacting radar with hart protocol
Hide thumbs Also See for Rosemount 5408:
Table of Contents

Advertisement

Reference Manual
00809-0100-4408
Table 7-1: Status - Failed
LCD display
Host diagnostic
message
message
MEAS
Level Measurement Lost No valid level reading. Reasons may
FAILUR
CONFG
Configuration Error
ERROR
Table 7-2: Configuration Error Details
Host diagnostic message
Volume Configuration Error
Scaled Variable Configuration
Error
Rosemount 5408 and 5408:SIS Level Transmitters
(continued)
Description
be multiple:
No valid surface echo peak in
the measuring range.
Incorrect device configuration.
The device has detected a
configuration error. Reasons may be
multiple (see
Description
The volume cannot be calculated correctly
with the current configuration.
The Scaled Variable configuration is
incorrect.
Recommended actions
1. Analyze the Echo Curve at time
2. Check device physical
3. Consider increasing
4. Restart the device.
5. Restore default settings and
6. If the condition persists,
1. Click the Details button for
Table 7-2
for details).
2. Correct the parameter causing
Recommended actions
1. If strapping table is used, check that
level-volume values are entered in
increasing order.
2. If strapping table is used, check that
number of strapping points to use is
correct.
3. If tank dimensions are used for
volume, check that geometry shape
and size measures are correct.
4. If condition persists, restore default
settings and reconfigure the device.
1. Check that the value pairs in the
scaled variable table are entered in
increasing order.
2. Check the number of table points to
use is correct.
3. If condition persists, restore default
settings, and reconfigure the device.
Service and troubleshooting
February 2020
of loss for reason and check
device configuration,
especially thresholds.
installation (for instance
antenna contamination).
Measurement Recovery Time
parameter for intermittent
conditions.
reconfigure the device.
replace the device.
more information.
the error.
103