Reference Manual
00809-0100-4408
Procedure
1. Under Configure, select Level Setup → Advanced.
2. Under More Advanced Options, select Expert Options.
3. Select the Holding Registers tab.
4. Under Show registers by, do one of the following:
5. Select Refresh.
6. To change a holding register value, type a new value in the corresponding value
7. Select Save to store the new value.
View/edit holding registers using AMS Device Manager and
handheld communicator
The holding registers store various transmitter parameters, such as configuration data,
used to control the measurement performance.
Prerequisites
Note
Do not use holding registers to configure the transmitter unless you are qualified. This
dialog is mainly used for service purposes and for advanced configuration.
Procedure
1. To view a holding register value:
2. To edit a holding register value:
Rosemount 5408 and 5408:SIS Level Transmitters
•
Select Block, and then in the list, select the desired register group.
Select Number, and then type the desired register number and the number of
•
registers.
field, or select a new value from the corresponding list.
a) Select Configure → Manual Setup → Level Setup → Advanced → Expert
Options → Holding Registers.
b) Type the desired register number to start reading from.
c) Select Read Holding Registers. 10 registers will be read, starting from the
selected number.
d) (Handheld communicator) Select Holding Registers.
a) Select Configure → Manual Setup → Level Setup → Advanced → Expert
Options → Holding Registers.
b) Select Write Holding Register and follow the on-screen instructions.
Service and troubleshooting
February 2020
131