Quick Start Guide
00825-0300-4408, Rev BA
May 2019
Rosemount
5408 and 5408:SIS Level
Transmitters
Parabolic Antenna

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Rosemount 5408

  • Page 1 Quick Start Guide 00825-0300-4408, Rev BA May 2019 ™ Rosemount 5408 and 5408:SIS Level Transmitters Parabolic Antenna...
  • Page 2: Table Of Contents

    Components of the parabolic antenna..................6 Mount the transmitter........................8 Adjust the inclination of the antenna..................17 Connect the air purging......................20 Adjust display orientation (optional)..................21 Prepare the electrical connections....................22 Connect wiring and power up.....................29 Configure transmitter using Guided Setup................. 33 Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 3: About This Guide

    May 2019 Quick Start Guide About this guide This Quick Start Guide provides basic guidelines for the Rosemount 5408 and 5408:SIS Level Transmitters. Refer to the Rosemount 5408 and 5408:SIS ® ™ with HART Reference Manual and Rosemount 5408 with F...
  • Page 4 This is true for all systems used within the facility. CAUTION Hot surfaces The flange and process seal may be hot at high process temperatures. Allow to cool before servicing. Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 5: Confirm Approval Type

    May 2019 Quick Start Guide Confirm approval type For hazardous locations transmitters labeled with multiple approval types: Procedure Permanently mark the checkbox of the selected approval type(s). Figure 2-1: Label with Multiple Approval Types Quick Start Guide...
  • Page 6: Components Of The Parabolic Antenna

    Components of the threaded version Figure 3-1: Components A. Antenna B. Purge plug kit C. Threaded sleeve D. M20 adapter E. Lock nut BSPP (G) 3½-in. F. Antenna adapter with ball joint G. O-ring Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 7 May 2019 Quick Start Guide Components of the welded version Figure 3-2: Components A. Antenna B. Purge plug kit C. Threaded sleeve D. M20 adapter E. Weld protection plate F. Flange ball G. O-ring H. Clamp flange I. Washer J. M8 screw K.
  • Page 8: Mount The Transmitter

    2. Lower the flange and antenna assembly into the nozzle. 3. Tighten the bolts and nuts with sufficient torque for the flange and gasket choice. Postrequisites 1. Adjust the inclination of the antenna (see Adjust the inclination of antenna). Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 9 May 2019 Quick Start Guide 2. Connect the air purging system (see Connect the air purging). Mount the threaded version Procedure 1. Remove the lock nut. 2. Mount the O-ring. 3. Mount the antenna adapter on flange/manhole cover. Ensure the antenna adapter fits tightly to the flange/manhole cover.
  • Page 10 Quick Start Guide May 2019 4. Remove the M20 adapter and visually inspect the O-rings for damage and dirt. 5. Carefully insert the antenna. 6. Secure the antenna. Torque 180 in-lb (20 N-m) 27 mm Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 11 May 2019 Quick Start Guide 7. Tighten the set screw. Torque 5 in-lb (0.5 N-m) H2 mm 8. Place a suitable gasket on the tank flange. 9. Lower the antenna assembly into the tank. 10. Tighten the bolts and nuts with sufficient torque for the flange and gasket choice.
  • Page 12 1. Mount the protection plates to flange/manhole cover. These plates protect the internal surfaces of the flange ball from dust and sparks during welding. A. Ø 3.94 ± 0.02 in. (Ø 100 ± 0.5 mm) B. Max. 1.18 in. (30 mm) Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 13 May 2019 Quick Start Guide 2. Weld the flange ball. 3. Remove the protection plates and visually inspect the internal surfaces of the flange ball for damage and dirt. 4. Mount the O-ring. Quick Start Guide...
  • Page 14 Insert the ball joint and place the clamp flange with the “7 Nm” marking side up. b) Gradually tighten the M8 screws. Torque 65 in-lb (7 N-m) H6 mm 6. Remove the M20 adapter and visually inspect the O-rings for damage and dirt. Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 15 May 2019 Quick Start Guide 7. Carefully insert the antenna. 8. Secure the antenna. Torque 180 in-lb (20 N-m) 27 mm 9. Tighten the set screw. Torque 5 in-lb (0.5 N-m) H2 mm Quick Start Guide...
  • Page 16 12. Tighten the bolts and nuts with sufficient torque for the flange and gasket choice. Postrequisites 1. Adjust the inclination of the antenna (see Adjust the inclination of antenna). 2. Connect the air purging system (see Connect the air purging). Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 17: Adjust The Inclination Of The Antenna

    May 2019 Quick Start Guide Adjust the inclination of the antenna Prerequisites WARNING Contents may be under pressure. • Do not loosen the M8 screws while in operation. Attempting to do so may release pressurized gases, resulting in serious injury or death. Procedure 1.
  • Page 18 May 2019 3. Place the supplied circular level on top of the antenna assembly. 4. Adjust the inclination of the antenna. 5. Gradually tighten the M8 screws. Torque 65 in-lb (7 N-m) H6 mm Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 19 May 2019 Quick Start Guide 6. Remove the circular level. 7. Mount the transmitter head. Align the marking on the sensor module with the air purge connection. Torque 355 in-lb (40 N-m) 60 mm 36 mm Quick Start Guide...
  • Page 20: Connect The Air Purging

    D. Use thread sealant or gasket according to your site procedures. E. G3/8-in. F. 0.3-0.4 in. (8-10 mm) (gasket excluded) Table 6-1: Incoming Air Supply Specification Maximum pressure Recommended pressure 190 psi (13 bar) 100 to 115 psi (7 to 8 bar) Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 21: Adjust Display Orientation (Optional)

    May 2019 Quick Start Guide Adjust display orientation (optional) To improve field access to wiring or to better view the optional LCD display: Prerequisites Note In high vibration applications, the transmitter housing must be fully engaged into the sensor module to meet the vibration test specifications. This is achieved by rotating the transmitter housing clockwise to thread limit.
  • Page 22: Prepare The Electrical Connections

    Failure to do so may impair the protection provided by the equipment. Transmitter housing The most effective grounding method is direct connection to earth ground with minimal impedance. There are two grounding screw connections provided (see Figure 8-1). Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 23 May 2019 Quick Start Guide Figure 8-1: Ground Screws A. Internal ground screw B. External ground screw Signal cable shield grounding Make sure the instrument cable shield is: • Trimmed close and insulated from touching the transmitter housing. • Continuously connected throughout the segment. •...
  • Page 24 Maximum loop resistance is determined by the voltage level of the external power supply. Figure 8-3: Load Limits Maximum Loop Resistance = 43.5 * (External Power Supply Voltage - 12) A. Loop Resistance (Ohms) B. External Power Supply Voltage (Vdc) Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 25 May 2019 Quick Start Guide Wiring diagram ® Figure 8-4: 4-20 mA/HART Communication A. Handheld communicator B. Approved IS barrier (for Intrinsically Safe installations only) C. HART modem D. Load resistance (≥250 Ω) E. Current meter F. Power supply Quick Start Guide...
  • Page 26 B. Approved IS barrier (for Intrinsically Safe installations only) C. HART modem D. Load resistance (≥250 Ω) E. Current meter F. Power supply G. Blue plug H. TEST terminal Note Blue plug must only be disconnected during loop current measurement procedure. Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 27 May 2019 Quick Start Guide ™ Figure 8-6: F Fieldbus OUNDATION A. Handheld communicator B. Approved IS barrier (for Intrinsically Safe installations only) C. F Fieldbus modem OUNDATION D. Power supply The terminals are not polarity sensitive. Quick Start Guide...
  • Page 28 B. Cable shield (insulate from touching the transmitter housing) C. Built-in terminator (connect jumper if last device on the fieldbus segment) D. Daisy-chain connection to other devices E. Handheld communicator F. Fieldbus modem G. Power supply ™ H. Rosemount 2410 Tank Hub Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 29: Connect Wiring And Power Up

    May 2019 Quick Start Guide Connect wiring and power up Procedure Verify the power supply is disconnected. 2. Remove the cover. 3. Remove the plastic plugs. 4. Pull the cable through the cable gland/conduit. Identification of thread size and type: Unless marked, the conduit/cable entries in the transmitter housing use a ½–14 NPT thread form.
  • Page 30 Apply PTFE tape or other sealant to the threads. Note Make sure to arrange the wiring with a drip loop. 8. Seal any unused ports with the enclosed metal plug. Apply PTFE tape or other sealant to the threads. Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 31 May 2019 Quick Start Guide 9. Attach and tighten the cover. a) Verify the cover jam screw is completely threaded into the housing. H2.5 mm b) Attach and tighten the cover. Make sure the cover is fully engaged. There should be no gap between the cover and the housing.
  • Page 32 May 2019 d) Turn the jam screw an additional ½ turn counterclockwise to secure the cover. 10. Connect the power supply. Note It may take up to 15 seconds before the LCD display lights up. Rosemount 5408 and 5408:SIS Level Transmitters...
  • Page 33: Configure Transmitter Using Guided Setup

    The FDI Package or DD is typically installed together with the configuration tool. The latest FDI Package is available at Emerson.com/RosemountRadarMasterPlus. The latest DD is available at Emerson.com/DeviceInstallKits. 10.4 Configure using Rosemount Radar Master Plus The options available in the Guided Setup wizard include all items required for basic operation.
  • Page 34 1. Turn on the handheld communicator and connect to the device. 2. Select Configure → Guided Setup. 3. Select Basic Setup and follow the on-screen instructions. 10.7 Learn more Visit Emerson.com/Rosemount to download the Rosemount 5408 and ® 5408:SIS with HART Reference Manual and Rosemount 5408 with ™ Fieldbus Reference Manual.
  • Page 35 May 2019 Quick Start Guide Quick Start Guide...
  • Page 36 The Emerson logo is a S-435 33 Mölnlycke trademark and service mark of Emerson Electric Sweden Co. Rosemount is mark of one of the Emerson +46 31 337 00 00 family of companies. All other marks are the +46 31 25 30 22...