Emerson Rosemount 5408 Reference Manual page 171

Level transmitters, non-contacting radar with hart protocol
Hide thumbs Also See for Rosemount 5408:
Table of Contents

Advertisement

Reference Manual
00809-0100-4408
Power
Advisory
Scaled
Variable
User Defined
Variable
A.2.5
Process temperature and pressure rating
The following figures give the maximum process temperature (measured at the lower part
of the flange, Tri-Clamp
antenna types.
Final rating may be lower depending on flange selection.
For antenna type code CAB, at 100 °F (38 °C), the rating decreases with increasing
temperature per ASME B16.5 Table 2-2.2, Class 300.
Note
For applications where saturated steam may occur, consult factory.
Figure A-4: Cone Antenna (PTFE Seal)
A
1450
(100)
725
(50)
562
(38.5)
363
(25)
44 (3)
-15 (-1)
-76
(-60)
A. Pressure psig (bar)
B. Temperature °F (°C)
C. Code CAC
D. Code CAB
E. Code CAA
F. Code CAD
Rosemount 5408 and 5408:SIS Level Transmitters
of signal strength. Signal Quality is available as output variable and it
comes with user configurable alerts.
The transmitter automatically measures and monitors the input
voltage. If the voltage is too low, operators will be provided with an
early alert.
The scaled variable configuration allows the user to convert a
transmitter variable into an alternative measurement, such as flow,
mass, or calibrated level (e.g. five-point point verification).
Allows designating more than 200 variables in the device as output
variable.
®
, or threaded connection) and pressure rating for different
-40
100
212
(-40)
(38)
(100)
Specifications and reference data
B
302
392
482
(150)
(200)
(250)
February 2020
C
D
E
F
171