3 Communications Data for CompoWay/F
Variable
Address
type
C3 (83)
0073
C3 (83)
0076
C3 (83)
0077
C3 (83)
0083
C3 (83)
0084
C3 (83)
0085
C3 (83)
0086
C3 (83)
0087
C3 (83)
0088
C3 (83)
0089
C3 (83)
008A
C3 (83)
008B
C3 (83)
008C
C3 (83)
008E
3 - 16
Parameter name
PV/SP No. 1 Display
H'00000000 (0): Nothing displayed.
Selection
H'00000001 (1): PV/SP
H'00000002 (2): PV
H'00000003 (3): PV/SP (character display)
H'00000004 (4): PV/SP/MV (heating)
H'00000005 (5): PV/SP/Multi-SP No.
H'00000006 (6): PV/SP/Soak time remain
H'00000007 (7): PV/SP/Internal SP (ramp SP)
H'00000008 (8): PV/SP/Alarm value 1
H'00000009 (9): PV/SP/MV (cooling)
PV Status Display
H'00000000 (0): OFF
Function
H'00000001 (1): Manual
H'00000002 (2): Stop
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Alarm 1 to 4 OR status
H'00000008 (8): Heater alarm
SV Status Display
H'00000000 to H'00000008 (0 to 8)
Note: Same as for PV Status Display
Function
Function
Display Refresh
H'00000000 (0): OFF
Period
H'00000001 (1): 0.25
H'00000002 (2): 0.5
H'00000003 (3): 1.0
Alarm 4 Type
H'00000000 to H'00000011 (0 to 17)
Note: Same settings as the Alarm 1 Type.
However, the LBA (loop burnout alarm)
cannot be set.
Event Input
H'00000000 to H'0000000D (0 to 13)
Note: Same as for Event Input Assignment 1.
Assignment 5
Event Input
H'00000000 to H'0000000D (0 to 13)
Note: Same as for Event Input Assignment 1.
Assignment 6
Auxiliary Output 4
H'00000000 (0): Close in alarm
Open in Alarm
H'00000001 (1): Open in alarm
Alarm 4 Hysteresis
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Moving Average
H'00000000 (0): OFF
Count
H'00000001 (1): 2 times
H'00000002 (2): 4 times
H'00000003 (3): 8 times
H'00000004 (4): 16 times
H'00000005 (5): 32 times
Alarm 4 Latch
H'00000000 (0): OFF
H'00000001 (1): ON
Alarm 4 ON delay
H'00000000 to H'000003E7 (0 to 999)
Alarm 4 OFF delay
H'00000000 to H'000003E7 (0 to 999)
Transfer Output
H'00000000 (0): 4 to 20 mA
H'00000001 (1): 1 to 5 V
Signal
Setting (monitor) value
E5@D Digital Temperature Controllers Communications Manual (H225)
Level
Advanced
function
setting
Initial setting
Advanced
function setting
Initial setting
Advanced
function setting
Initial setting